Product information
Overview
Key Features
- Rated power and overload: Rated power: 75.00 kW (LO) or 55.00 kW (HO); the collected description states 150% overload for 3 s.
- Supply and output: Input: 380 … 480 V +10 % -20 %, 3 AC, 47 … 63 Hz. Output: 3 AC, with 0 … 240 Hz for vector control and 0 … 550 Hz for V/f control.
- Control and communication: Control includes V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control. Communication: PROFINET, EtherNet/IP.
- I/O and safety: I/O includes 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output. Safe Torque Off is integrated.
- Connections and motor cable: Line-side and motor-end connections use screw-type terminals. Maximum shielded motor cable length: 300 m (984.25 ft).
- Mechanical configuration and protection: Frame size: FSF. Dimensions: 305 mm width and 357 mm depth. Degree of protection: IP20 / UL open type.
Technical Summary
| Product | SINAMICS G120C compact converter |
|---|---|
| Order number | 6SL3210-1KE31-4UF1 |
| Rated power (LO) | 75.00 kW | 75.00 hp |
| Rated power (HO) | 55.00 kW | 60.00 hp |
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Output frequency | 0 … 240 Hz for vector control; 0 … 550 Hz for V/f control |
| Communication | PROFINET, EtherNet/IP |
| I/O | 6 DI, 1 fail-safe DI, 1 relay changeover contact, 1 transistor output, 1 differential AI, 1 non-isolated AO |
| Safe Torque Off | Integrated |
| Cooling | Air cooling using an integrated fan |
| Degree of protection | IP20 / UL open type |
Frequently Asked Questions
What is the rated power of Siemens 6SL3210-1KE31-4UF1?
Rated power is 75.00 kW | 75.00 hp (LO) or 55.00 kW | 60.00 hp (HO).
Which control methods does this SINAMICS G120C support?
It supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control.
Which communication interfaces are available?
Communication interfaces are PROFINET and EtherNet/IP.
What protection and motor cable length are specified?
Degree of protection is IP20 / UL open type. Maximum shielded motor cable length is 300 m (984.25 ft).