Product information
Overview
Key Features
- Low-overload output rating: Rated power: 3.00 kW | 4.00 hp at low overload, with 150% for 3s, 110% for 57s and 100% for 240s.
- High-overload output rating: Rated power: 2.20 kW | 3.00 hp at high overload, with 200% for 3s, 150% for 57s and 100% for 240s.
- Supply and communication: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Communication: PROFINET and EtherNet/IP.
- I/O and safety: Interface: 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output. Safe Torque Off is integrated.
- Control and mechanical data: Supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control. Frame size: FSA; dimensions: 73 mm width and 200 mm depth; protection: IP20 / UL open type.
Technical Summary
| Product | 6SL3210-1KE17-5UF1 |
|---|---|
| Product family | SINAMICS G120C |
| Low-overload rated power | 3.00 kW | 4.00 hp |
| High-overload rated power | 2.20 kW | 3.00 hp |
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Communication | PROFINET, EtherNet/IP |
| I/O | 6DI, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, 1 non-isolated analog output |
| Control | V/f linear / square-law / parameterizable; V/f with flux current control (FCC); V/f ECO linear / square-law; sensorless vector control |
| Protection | IP20 / UL open type |
| Frame size | FSA |
| Integrated safety | Safe Torque Off |
Frequently Asked Questions
What is the exact Siemens model and product family?
The exact model is Siemens 6SL3210-1KE17-5UF1 from the SINAMICS G120C family.
What are the low-overload and high-overload power ratings?
Low overload is 3.00 kW | 4.00 hp; high overload is 2.20 kW | 3.00 hp. The stated overload durations and percentages apply to each rating.
Which communication and I/O interfaces are provided?
Communication is PROFINET and EtherNet/IP. The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output.
What quantity, destination and requested date should be included for a quotation?
Please include the required quantity, destination and requested date so the model-specific quotation can be reviewed.