Product information
Overview
Key Features
- Rated power and overload: Rated power: 2.20 kW | 3.00 hp at low overload and 1.50 kW | 2.00 hp at high overload. Low overload: 150% for 3s, 110% for 57s, 100% for 240s; high overload: 200% for 3s, 150% for 57s, 100% for 240s.
- Supply and output: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, rated voltage 400V IEC | 480V NEC 1).
- Control techniques: Supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control.
- I/O and communication: I/O: 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog/digital input and 1 non-isolated analog output. Communication: PROFINET, EtherNet/IP.
- Connections and motor cable: Line-side and motor-end connections use plug-in screw terminals. Maximum shielded motor cable length: 50 m (164.04 ft).
- Protection and mechanical data: Protection: IP20 / UL open type. Frame size: FSAA. Dimensions: 73 mm width x 160 mm depth; net weight: 1.40 kg (3.09 lb).
Technical Summary
| Product | Siemens 6SL3210-1KE15-8AF2 SINAMICS G120C |
|---|---|
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated power (LO) | 2.20 kW | 3.00 hp |
| Rated power (HO) | 1.50 kW | 2.00 hp |
| Communication | PROFINET, EtherNet/IP |
| I/O | 6DI, 2DO, 1AI, 1AO, 1 fail-safe digital input |
| Control | V/f linear / square-law / parameterizable; sensorless vector control |
| Integrated filter | Class A |
| Protection | IP20 / UL open type |
| Frame size | FSAA |
Frequently Asked Questions
What is the exact product identity?
It is Siemens 6SL3210-1KE15-8AF2, a SINAMICS G120C compact converter.
What input supply does this converter use?
Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz.
What communication and I/O are provided?
Communication: PROFINET and EtherNet/IP. I/O includes 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog/digital input and 1 analog output.
What are the overload ratings?
Low overload: 2.20 kW | 3.00 hp; high overload: 1.50 kW | 2.00 hp, with the stated overload durations in the configuration data.
What details should I provide for a quotation?
Please provide the required quantity, destination and requested date for model-specific quotation support.