Product information
Overview
Key Features
- Low- and high-overload ratings: Rated output power is 2.20 kW at low overload and 1.50 kW at high overload, with the supplied overload sequences of 150% 3s, 110% 57s, 100% 240s and 200% 3s, 150% 57s, 100% 240s.
- 3 AC electrical ratings: Input is 3 AC, 380 … 480 V +10 % -20 % at 47 … 63 Hz. Output is 3 AC with rated currents of 5.60 A (LO) and 4.10 A (HO).
- Control and communication: Supported control techniques include V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control. Communication is USS/MODBUS RTU.
- Integrated I/O and safety: The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input with 10 bit resolution, and 1 non-isolated analog output.
- Connections and motor cable: Line, motor-end, and DC link connections use plug-in screw terminals. The maximum shielded motor cable length is 50 m (164.04 ft).
- Mechanical and protection configuration: Frame size is FSAA. Dimensions are 73 mm (2.87 in) wide and 155 mm (6.10 in) deep. Protection is IP20 / UL open type.
Technical Summary
| Order number | 6SL3210-1KE15-8AB2 |
|---|---|
| Product lifecycle | Active Product |
| Input supply | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated output power (LO) | 2.20 kW | 3.00 hp |
| Rated output power (HO) | 1.50 kW | 2.00 hp |
| Maximum output current | 8.20 A |
| Output frequency for vector control | 0 … 240 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Communication | USS/MODBUS RTU |
| Integrated filter | Class A |
| Protection | IP20 / UL open type |
| Frame size | FSAA |
Frequently Asked Questions
What are the low- and high-overload output ratings of 6SL3210-1KE15-8AB2?
Low overload is 2.20 kW at 150% 3s, 110% 57s, 100% 240s. High overload is 1.50 kW at 200% 3s, 150% 57s, 100% 240s.
Which control techniques and communication interface does it have?
It supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control. Communication is USS/MODBUS RTU.
What I/O is included?
It has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input with 10 bit resolution, and 1 non-isolated analog output.
What are the connections and protection details?
Line, motor-end, and DC link connections use plug-in screw terminals. Protection is IP20 / UL open type, and the maximum shielded motor cable length is 50 m (164.04 ft).
What information should I provide for a quotation?
Please provide the required quantity, destination, requested date, and project or model list for quotation review.