Product information
Overview
Key Features
- Rated power: 1.50 kW | 2.00 hp at low overload; 1.10 kW | 1.50 hp at high overload.
- Input and output ratings: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, 400V IEC | 480V NEC.
- Overload capacity: Low overload: 150% for 3s, 110% for 57s, 100% for 240s. High overload: 200% for 3s, 150% for 57s, 100% for 240s.
- I/O and safety: 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output. Safe Torque Off is integrated.
- Control and communication: PROFIBUS DP; V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control.
- Connections and protection: Plug-in screw terminals; IP20 / UL open type. Maximum shielded motor cable length: 150 m (492.13 ft).
Technical Summary
| Product | 6SL3210-1KE14-3UP2 |
|---|---|
| Product family | SINAMICS G120C |
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated power, LO | 1.50 kW | 2.00 hp |
| Rated power, HO | 1.10 kW | 1.50 hp |
| Communication | PROFIBUS DP |
| Digital inputs | 6 standard; 1 fail-safe |
| Analog input | 1 differential input, 10 bit |
| Protection | IP20 / UL open type |
| Frame size | FSAA |
Frequently Asked Questions
What is the exact Siemens model and product family?
The exact model is 6SL3210-1KE14-3UP2 from the SINAMICS G120C family.
What are the input voltage and frequency ratings?
Input is 3 AC, 380 … 480 V +10 % -20 %, at 47 … 63 Hz.
What communication and I/O are provided?
The converter has PROFIBUS DP, 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output.
What protection and motor cable length are specified?
Protection is IP20 / UL open type. The maximum shielded motor cable length is 150 m (492.13 ft).
What quantity, destination and requested date should be included for a quotation?
Include the required quantity, destination and requested date with your Siemens requirement.