Product information
Overview
Key Features
- High-overload output: Rated power is 30.00 kW | 40.00 hp (HO), with 200% for 3 s, 150% for 57 s and 100% for 240 s at an ambient temperature of 0 … 50 °C.
- Light-overload output: Rated power is 37.00 kW | 50.00 hp (LO), with 150% for 3 s, 110% for 57 s and 100% for 240 s at an ambient temperature of 0 … 40 °C.
- Input and output ratings: Input and output each have 3 AC phases. Line voltage is 380 … 480 V ±10 % and line frequency is 47 … 63 Hz.
- Control frequency ranges: Output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control. Pulse frequency is 4 kHz.
- Connections and cable lengths: Line-side and motor-end connections use M6 bolts with 10.00 … 50.00 mm2 (AWG 8 … AWG 1) conductors. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.
- Mechanical configuration and protection: Frame size is FSE. Dimensions are 635 mm high × 275 mm wide × 204 mm deep, with IP20 / UL open type protection and 21.00 kg net weight. The unit is without a control unit and BOP.
Technical Summary
| Product type | SINAMICS G120 PM250 power module |
|---|---|
| Lifecycle | Active Product |
| High-overload rated power | 30.00 kW | 40.00 hp (HO) |
| Light-overload rated power | 37.00 kW | 50.00 hp (LO) |
| Line voltage | 380 … 480 V ±10 % |
| Line frequency | 47 … 63 Hz |
| Output frequency for vector control | 0 … 200 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Connections | M6 bolt, line side and motor end |
| Degree of protection | IP20 / UL open type |
Frequently Asked Questions
What is Siemens 6SL3225-0BE33-0AA0?
It is a SINAMICS G120 PM250 power module with an integrated Class A filter and regeneration capability.
What are the high-overload and light-overload ratings?
High overload is 30.00 kW | 40.00 hp (HO); light overload is 37.00 kW | 50.00 hp (LO). Their specified overload durations and ambient-temperature conditions apply.
What connections and motor cable lengths does it support?
Both the line side and motor end use M6 bolts and 10.00 … 50.00 mm2 (AWG 8 … AWG 1) conductors. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.
Is the control unit and BOP included?
It is without a control unit and BOP. For a quotation, send the required quantity, destination and requested date.