Product information
Overview
Key Features
- Power and overload ratings: Rated output power: 7.50 kW | 10.00 hp (LO) or 5.50 kW | 7.50 hp (HO). Power high overload: 5.5 kW at 200% for 3 s, 150% for 57 s and 100% for 240 s; ambient temperature 0 … 50 °C. Power low overload: 7.5 kW at 150% for 3 s, 110% for 57 s and 100% for 240 s; ambient temperature 0 … 40 °C.
- Input and output: Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz. Output: 3 AC, with rated current 18.00 A (LO), 13.20 A (HO) and maximum output current 26.40 A.
- Control performance: Output frequency: 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control. Pulse frequency: 4 kHz.
- Energy recovery and filter: The PM 250 has energy recovery capability and an integrated Class A filter.
- Connections and motor cable: Line-side and motor-end connections use screw-type terminals for 2.50 … 10.00 mm2 (AWG 14 … AWG 8) conductors. Maximum motor cable length: 25 m (82.02 ft) shielded or 100 m (328.08 ft) unshielded.
- Mechanical configuration and protection: Frame size: FSC. Dimensions: 334 mm H × 189 mm W × 185 mm D. Degree of protection: IP20 / UL open type. The unit is without a Control Unit and BOP.
Technical Summary
| Product type | SINAMICS G120 Power Module PM 250 |
|---|---|
| Input supply | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Rated output power (LO) | 7.50 kW | 10.00 hp |
| Rated output power (HO) | 5.50 kW | 7.50 hp |
| Output frequency, vector control | 0 … 200 Hz |
| Output frequency, V/f control | 0 … 550 Hz |
| Integrated filter | Class A |
| Energy recovery | Capable of energy recovery |
| Frame size | FSC |
| Degree of protection | IP20 / UL open type |
| Configuration exclusion | Without Control Unit and BOP |
Frequently Asked Questions
What is Siemens 6SL3225-0BE25-5AA1?
It is a SINAMICS G120 PM 250 Power Module with an integrated Class A filter and energy recovery capability.
What are the low-overload and high-overload output ratings?
Low overload is 7.50 kW | 10.00 hp; high overload is 5.50 kW | 7.50 hp. The high-overload profile is 200% for 3 s, 150% for 57 s and 100% for 240 s at 0 … 50 °C. The low-overload profile is 150% for 3 s, 110% for 57 s and 100% for 240 s at 0 … 40 °C.
What connections and motor cable lengths are supported?
Both line-side and motor-end connections use screw-type terminals for 2.50 … 10.00 mm2 (AWG 14 … AWG 8) conductors. Maximum motor cable length is 25 m (82.02 ft) shielded or 100 m (328.08 ft) unshielded.
What is included in the configuration?
It is without a Control Unit and BOP.
How can I request a quotation for this exact model?
Send the required quantity, destination and requested date for an MRO or project quotation.