Product information
Overview
Applications
- Safety-oriented shutdown of load groups: The module supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015.
Key Features
- 4 analog output channels: The AQ 4xU/I HF module has 4 analog output channels.
- 16-bit resolution and accuracy: Resolution with overrange is up to 16 bit, with 0.1% accuracy.
- Voltage and current ranges: Supported ranges include 0 to 10 V, 1 V to 5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
- Diagnostics and substitute values: The module has diagnostics, diagnostic alarms, supply-voltage monitoring and connectable substitute values. Wire-break diagnosis applies only to current output; short-circuit diagnosis applies only to voltage output.
- S7-1500 integration: Engineering is supported with STEP 7 TIA Portal from V14 and STEP 7 from V5.5 SP3. The module supports PROFINET from GSD V2.3 and PROFIBUS from GSD V1.0.
Technical Summary
| Product type | AQ 4xU/I HF |
|---|---|
| Channels | 4 analog output channels |
| Resolution | Up to 16 bit with overrange |
| Accuracy | 0.1% |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V DC to 28.8 V DC |
| Output ranges | 0 to 10 V; 1 V to 5 V; -10 V to +10 V; 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Cycle time | 125 μs for all channels, independent of the number of activated channels |
| Firmware version | V1.1.0 |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7532-5ND00-0AB0?
It is a SIMATIC S7-1500 AQ 4xU/I HF analog output module.
Which output ranges does the module support?
It supports 0 to 10 V, 1 V to 5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA and 4 mA to 20 mA.
What is included with the module?
Delivery includes the infeed element, shielding bracket and shield terminal. The front connector with screw terminals or push-in terminals must be ordered separately.
What information should be included for a quotation request?
Please provide the required quantity, destination and project-list context for quotation verification.