Overview
Key Features
- 16 voltage input channels: The module has 16 analog inputs, all for voltage measurement, with 16 channels in groups of 16.
- 16-bit resolution: Resolution with overrange, including sign, is up to 16 bit.
- Supported voltage ranges: Supported ranges include 1 V to 5 V, -1 V to +1 V, -10 V to +10 V and -5 V to +5 V.
- Diagnostics and interrupts: The module has diagnostics, diagnostic alarms, limit value alarms, hardware interrupts, overflow/underflow detection and wire-break detection for 1 V to 5 V.
- Integration and filtering: Integration time is parameterizable, with selectable values of 2,5 / 16,67 / 20 / 100 ms; four parameterizable smoothing levels are available.
- Delivery and connector configuration: Delivery includes the infeed element, shield bracket and shield terminal. The front connector with screw terminals or push-in must be ordered separately.
Technical Summary
| Product type | AI 16xU BA |
|---|---|
| Product lifecycle | Active Product |
| Analog inputs | 16 |
| Voltage measurement inputs | 16 |
| Resolution with overrange | 16 bit |
| Operational error limit | 0.5 % relative to input range |
| Supported voltage ranges | 1 V to 5 V; -1 V to +1 V; -10 V to +10 V; -5 V to +5 V |
| Input resistance | 10 MΩ for 1 V to 5 V, -1 V to +1 V, -10 V to +10 V and -5 V to +5 V |
| Common mode voltage, max. | 4 V |
| Power consumption from the backplane bus | 0.85 W |
| Firmware version | V1.0.0 |
| Front connector | To be ordered separately |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7531-7LH00-0AB0?
It is a SIMATIC S7-1500 analog input module with product type designation AI 16xU BA.
Which voltage ranges does the module support?
It supports 1 V to 5 V, -1 V to +1 V, -10 V to +10 V and -5 V to +5 V.
Is the front connector included?
It is not included; the front connector with screw terminals or push-in must be ordered separately.
What diagnostics are available?
The module has diagnostics, diagnostic alarms, limit value alarms, overflow/underflow detection and wire-break detection for 1 V to 5 V.
What should be included in a quotation request?
Provide the required quantity and destination for quotation support.