Product information
Overview
Applications
- Safety-oriented load-group shutdown: The substitute-value function supports safety-oriented shutdown of load groups up to SIL1 according to EN IEC 62061:2021 and Category 2 / PL c according to EN ISO 13849-1:2015.
Key Features
- 16 relay output channels: The digital output module has 16 relay channels with parameterizable digital outputs.
- 230 V AC output: Rated output voltage is 230 V AC; the supported range also includes 24 V DC to 120 V DC and 24 V AC to 230 V AC.
- Output current capacity: Rated output current for signal "1" is 2 A. Maximum current is 2 A per channel, 4 A per group, and 32 A per module; additional descriptions apply in the manual.
- 24 V supply: Rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC and reverse polarity protection.
- Diagnostics and status indication: The module has diagnostic and maintenance alarms, substitute values, supply-voltage monitoring, RUN, ERROR, MAINT and PWR LEDs, plus green channel-status display.
- Separate front connector: The front connector, available with screw terminals or push-in terminals, must be ordered separately.
Technical Summary
| Product type | DQ 16x 230 V AC/2 A ST (relay) |
|---|---|
| Digital outputs | 16 relay outputs |
| Rated output voltage | 230 V AC; 24 V DC to 120 V DC / 24 V AC to 230 V AC |
| Rated output current | 2 A for signal "1" |
| Maximum current per group | 4 A; see additional description in the manual |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Output address space | 2 byte |
| Firmware version | V1.1.0 |
| Communication support | PROFIBUS from GSD V1.0 / V5.1; PROFINET from GSD V2.3 / – |
| Front connector | Screw terminals or push-in terminals; to be ordered separately |
Frequently Asked Questions
What is the exact output configuration of 6ES7522-5HH00-0AB0?
It has 16 relay outputs rated at 230 V AC, with a rated output current of 2 A for signal "1".
What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC.
What is the maximum current per group?
The maximum current is 4 A per group; see the additional description in the manual.
Is the front connector included?
It is without a front connector. A connector with screw terminals or push-in terminals must be ordered separately.
What should be included in an inquiry?
Provide the required quantity, destination and project-list context for quotation review.