Applications
- S7-1500 backplane bus power supply: Supplies the backplane bus of the S7-1500 with operating voltage.
Key Features
- Backplane bus supply: Supplies the S7-1500 backplane bus with operating voltage and provides 60 W infeed power.
- Rated supply voltage: Rated supply voltage: 24 V / 48 V / 60 V DC.
- Supply voltage range: Permissible range: 19.2 V lower limit; Static 19.2 V, dynamic 18.5 V. Upper limit: 72 V; Static 72 V, dynamic 75.5 V.
- Protection: Reverse polarity protection, short-circuit protection, and output-current short-circuit protection: Yes.
- Installation temperature: Horizontal installation: -25 °C; up to FS04: 0 °C to 60 °C. Vertical installation: -25 °C; up to FS04: 0 °C to 40 °C.
- Engineering and firmware: Configurable/integrated with STEP 7 TIA Portal from V12 / V12 and STEP 7 from V5.5 SP3 or higher. Firmware version: from V1.0.0.
Technical Summary
| Product type | PS 60 W 24/48/60 V DC |
|---|---|
| Rated supply voltage | 24 V / 48 V / 60 V DC |
| Backplane bus infeed power | 60 W |
| Firmware version | from V1.0.0 |
| STEP 7 TIA Portal | Configurable/integrated from V12 / V12 |
| STEP 7 | Configurable/integrated from V5.5 SP3 or higher |
| Reverse polarity protection | Yes |
| Short-circuit protection | Yes |
| Horizontal installation | -25 °C; up to FS04: 0 °C to 60 °C |
| Vertical installation | -25 °C; up to FS04: 0 °C to 40 °C |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7505-0RA00-0AB0?
The product type designation is PS 60 W 24/48/60 V DC.
What supply voltage does this system power supply use?
The rated supply voltage is 24 V / 48 V / 60 V DC.
What power does it provide to the backplane bus?
The infeed power to the backplane bus is 60 W.
What installation temperature limits apply?
For horizontal installation, the range is -25 °C; up to FS04: 0 °C to 60 °C. For vertical installation, it is -25 °C; up to FS04: 0 °C to 40 °C.