Fail-Safe I/O Parts

6ES7136-6RA00-0BF0

Product details

Product Code
6ES7136-6RA00-0BF0
Dimensions
8 × 6.8 × 2.9 cm
Weight
0.07 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Pricing, condition, availability and delivery terms are confirmed against the exact product reference.

Product information

Overview

Key Features

  • Relay output configuration: 1 relay output with 2 NO contacts; digital output type: Relays.
  • Switching capacity: Maximum 5 A with resistive load, 25 W with lamp load, and 2 Hz with resistive load.
  • Supply and load voltage: Rated supply voltage: 24 V DC; load voltage: 24 V DC and 24 … 230 V AC.
  • Output current by installation conditions: For horizontal installation: maximum 5 A up to 40 °C, 4 A up to 50 °C, and 3 A up to 60 °C. For vertical installation: maximum 3 A up to 50 °C; see manual derating data.
  • Diagnostics and status: Diagnostics function, green/red DIAG LED, and green channel status LED.
  • Isolation and protection: Potential separation between channels, backplane bus, and electronics supply; 250 V AC between channels and backplane bus/supply voltage with reinforced insulation.

Technical Summary

Product type F-RQ 24 … 48VDC/24 … 230VAC/5A ST
Digital outputs 1 relay output; 2 NO contacts
Rated coil voltage 24 V DC
Load voltage 24 V DC and 24 … 230 V AC
Switching capacity, resistive load, max. 5 A
Supply voltage range 20.4 V to 28.8 V DC
BaseUnit BU type F0
Engineering STEP 7 TIA Portal from V13; STEP 7 from V5.5 SP4 and higher
PROFINET GSD version V2.31
Permissible potential difference 250 V AC (reinforced insulation)

Frequently Asked Questions

What is the exact product type of Siemens 6ES7136-6RA00-0BF0?

It is an F-RQ 24 … 48VDC/24 … 230VAC/5A ST SIMATIC ET 200SP relay output module.

How many relay outputs and contacts does the module have?

It has 1 relay output with 2 NO contacts.

What supply and load voltages does it support?

The rated coil supply is 24 V DC. The load voltage is 24 V DC and 24 … 230 V AC.

What output current is permitted for installation conditions?

For horizontal installation, the maximum total output current is 5 A up to 40 °C, 4 A up to 50 °C, and 3 A up to 60 °C. For vertical installation, it is 3 A up to 50 °C; see the manual for derating data.

What information should I provide for a quotation?

Provide the required quantity, destination, requested date, and any project list or verification requirements.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote