Fail-Safe I/O Parts

6ES7136-6AA00-0CA1

Product details

Product Code
6ES7136-6AA00-0CA1
Dimensions
7.7 × 6.8 × 2.7 cm
Weight
0.057 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Pricing, condition, availability and delivery terms are confirmed against the exact product reference.

Product information

Overview

Key Features

  • Fail-safe analog inputs: 4 analog inputs support current measurement with 0 to 20 mA and 4 mA to 20 mA input ranges.
  • Safety performance: The module achieves PLe and Cat. 4 according to ISO 13849-1 and SIL 3 according to IEC 61508 in safety mode.
  • Signal connection: Supports 2-wire and 4-wire transducers; the maximum burden of a 2-wire transmitter is 650 Ω.
  • Supply and encoder output: Rated supply voltage is 24 V DC. The encoder supply provides 24 V with 300 mA maximum output current for all encoders/channels.
  • Diagnostics: Diagnostics include supply-voltage monitoring, wire-break and short-circuit detection, diagnostic alarm, and green/red LED indications.
  • TIA Portal engineering: Configurable and integrated with STEP 7 TIA Portal from V15 with HSP 203; FW update is possible.

Technical Summary

Product type designation F-AI 4xI 0(4)..20mA 2-/4-wire HF
Analog inputs 4
Input ranges 0 to 20 mA; 4 mA to 20 mA
Rated supply voltage 24 V DC
Resolution with overrange 16 bit
Safety performance PLe, Cat. 4 according to ISO 13849-1; SIL 3 according to IEC 61508
Permissible ambient temperature 0 °C to 60 °C horizontal; 0 °C to 50 °C vertical
Compatible BaseUnits BU type A0, A1

Frequently Asked Questions

What is the exact product type of Siemens 6ES7136-6AA00-0CA1?

It is an F-AI 4xI 0(4)..20mA 2-/4-wire HF electronic module for SIMATIC ET 200SP.

Which input ranges does the module support?

It supports 0 to 20 mA and 4 mA to 20 mA current input ranges, with 4 analog inputs.

What safety levels are supported?

The module supports PLe and Cat. 4 according to ISO 13849-1 and SIL 3 according to IEC 61508 in safety mode.

Which BaseUnits can be used?

Usable BaseUnits are BU type A0 and BU type A1.

What information should I provide for a quotation?

Provide the required quantity, destination, requested date, and any project list or configuration details for verification.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote