Product information
Overview
Key Features
- Potential distribution: PotDis-TB-P1-R potential distributor module with 18 x potential P1.
- Rated voltage: P1 and P2 bus: 48 V maximum; process terminals: 48 V maximum.
- Current carrying capacity: 10 A maximum up to 60 °C, for the P1 and P2 bus, and for process terminals.
- Push-In connections: 16 process terminals to the I/O module and 2 terminals with connection to the P1 and P2 bus.
- Installation conditions: Operating temperature is -30 °C to 60 °C for horizontal installation and -30 °C to 50 °C for vertical installation.
Technical Summary
| Product type | PotDis-TB-P1-R potential distributor module |
|---|---|
| Potential P1 | 18 x |
| Maximum voltage, P1 and P2 bus | 48 V |
| Maximum voltage, process terminals | 48 V |
| Maximum current carrying capacity | 10 A up to 60 °C; 10 A for P1 and P2 bus; 10 A for process terminals |
| Process terminals | 16 to I/O module |
| P1 and P2 bus terminals | 2 |
| Terminal type | Push-In terminal |
| Conductor cross-section | 0.14 mm2 min.; 2.5 mm2 max. |
| Operating temperature | -30 °C to 60 °C horizontal; -30 °C to 50 °C vertical |
| External power-supply protection | 10 A miniature circuit breaker with type B or C tripping characteristic for the respective rated supply voltage |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7193-6TP00-0TP1?
It is a SIMATIC ET 200SP PotDis-TB-P1-R potential distributor module.
What voltage does the module support?
The maximum rated voltage is 48 V for the P1 and P2 bus and 48 V for the process terminals.
How many terminals are included?
It has 16 process terminals to the I/O module and 2 terminals connected to the P1 and P2 bus.
What installation temperatures are supported?
For horizontal installation, the operating range is -30 °C to 60 °C. For vertical installation, it is -30 °C to 50 °C.
What details should be provided for a quotation?
Provide the required quantity, destination and any project-list or configuration details for verification.