Product information
Overview
Applications
- Hazardous locations: The product declaration states use in hazardous locations.
- Maritime application: The product declaration includes maritime application under FM CCC-Ex.
Key Features
- BaseUnit Type C1: Product type designation: BU type C1, with 1 slot of Type C1 and automatic encoding.
- Push-in terminals and AUX terminals: The unit has Push-in terminals and 2 AUX terminals bridged to the left. The system-integrated shield connection is optional.
- Supply voltage options: Supply voltage is 24 V or 230 V for the P1 and P2 bus, AUX bus, and process terminals. AUX bus supply has equal potential grouping to the P1/P2 bus or PE.
- Current carrying capacity: Current carrying capacity is up to 10 A at up to 60 °C; process terminals support up to 5 A, or 10 A for process terminals 5 and 6.
- Process terminal capacity: The unit provides 16 process terminals to the I/O module, with 0 terminals to the AUX bus and 0 add-on terminals.
- Dimensions and isolation: Dimensions are 20 mm width, 117 mm height, and 35 mm depth. Potential separation exists between the backplane bus, process terminals, and supply voltage; isolation is tested with 3 100 V DC.
Technical Summary
| Product type | BU type C1 |
|---|---|
| Functional status | FS10 and higher |
| Supply voltage for P1 and P2 bus | 24 V or 230 V |
| Supply voltage for AUX bus | 24 V or 230 V; Equal potential group to P1/P2 bus or PE |
| Supply voltage for process terminals | 24 V or 230 V |
| Current carrying capacity | Up to 10 A at up to 60 °C; process terminals up to 5 A, 10 A for process terminals 5 and 6 |
| Terminals | Push-in terminal; 16 process terminals to I/O module |
| AUX terminals | 2; bridged to the left |
| Operating ambient temperature | -30 °C to 60 °C horizontal; -30 °C to 50 °C vertical |
| Isolation test | 3 100 V DC |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7193-6BP20-0BC1?
It is a SIMATIC ET 200SP BaseUnit Type C1, designated BU type C1.
Which supply voltages are supported?
The supply voltage options are 24 V or 230 V for the P1 and P2 bus, AUX bus, and process terminals.
How many terminals does the BaseUnit have?
It has 16 process terminals to the I/O module, 2 AUX terminals bridged to the left, 0 terminals to the AUX bus, and 0 add-on terminals.
What should be included in a quotation request?
Include the required quantity, destination, and project-list context so the exact configuration can be reviewed.