Product information
Overview
Applications
- Stepper-drive interface: Provides a pulse train output interface for stepper drives.
Key Features
- Pulse train output: 2 channels provide a PTO signal interface for stepper drives, including pulse and direction, count up/count down, and incremental encoder signal types.
- Digital I/O capacity: Each channel has 3 digital inputs and 3 digital outputs; digital inputs and outputs are parameterizable.
- 24 V supply: Rated supply voltage and load voltage L+ are 24 V DC; the permissible load-voltage range is 19.2 V to 28.8 V DC with reverse polarity protection.
- Output protection and diagnostics: Digital outputs have electronic/thermal short-circuit protection. Diagnostic alarms monitor supply voltage and short circuits, with PWR, channel-status, and DIAG LEDs.
- Engineering and BaseUnit: The module is configurable/integrated with STEP 7 V17 with HSP or higher and is suitable for BU type A0.
Technical Summary
| Product type | TM PTO 2x24V |
|---|---|
| Function | Interface module for stepper drives with 2 pulse train output channels |
| Digital inputs | 6; 3 per channel |
| Digital outputs | 6; 3 per channel |
| Supply voltage | 24 V DC rated |
| Load voltage L+ | 19.2 V to 28.8 V DC permissible range |
| PTO signal interface | 24 V asymmetrical |
| Maximum PTO switching frequency | 200 kHz; For 24 V PTO outputs |
| BaseUnit | BU type A0 |
| Engineering | STEP 7 V17 with HSP or higher |
| Protection | Electronic/thermal short-circuit protection |
| Product lifecycle | Active Product |
Frequently Asked Questions
What is the exact product type of 6ES7138-6EB00-0BA0?
It is a SIMATIC ET 200SP TM PTO 2x24V interface module for stepper drives.
How many I/O points does the module have?
It has 6 digital inputs and 6 digital outputs, with 3 inputs and 3 outputs per channel.
What supply voltage does this module use?
The rated supply voltage and load voltage L+ are 24 V DC. The permissible load-voltage range is 19.2 V to 28.8 V DC.
Which BaseUnit is suitable for this module?
It is suitable for BU type A0.
What information should I provide for a quotation?
Provide the required quantity, destination, requested date, and any project list or verification requirements.