Product information
Overview
Applications
- Driving analog actuators: The module provides voltage and current outputs for connecting actuators through supported two-wire and four-wire configurations.
Key Features
- Analog output capacity: 2 analog outputs support voltage ranges from -10 V to +10 V and current ranges from -20 mA to +20 mA.
- Resolution and speed: Resolution is up to 16 bit; minimum cycle time for all channels is 125 μs, with oversampling for 2 channels per module.
- Supply and protection: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Diagnostics: The module provides channel diagnostics, supply-voltage monitoring, wire-break detection for current output, and short-circuit detection for voltage output.
- Actuator connections: Supported connections include two-wire and four-wire voltage output and two-wire current output.
- Installation and configuration: The module is suitable for BU type A0, A1, has a Type A mechanical coding element, and supports STEP 7 TIA Portal from V13 SP1.
Technical Summary
| Product type | AQ 2xU/I HS |
|---|---|
| Analog outputs | 2 |
| Output resolution, max. | 16 bit |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Minimum cycle time, all channels | 125 μs |
| Oversampling | Yes; 2 channels per module |
| Supported BaseUnits | BU type A0, A1 |
| Channel diagnostics | Yes |
| Voltage output load impedance, min. | 2 kΩ |
| Current output load impedance, max. | 500 Ω |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7135-6HB00-0DA1?
It is the SIMATIC ET 200SP analog output module AQ 2xU/I HS.
What supply voltage does this module require?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which output ranges are supported?
Voltage ranges are 0 to 10 V, 1 V to 5 V, -5 V to +5 V, and -10 V to +10 V. Current ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
Which BaseUnits are supported?
The module is suitable for BU type A0, A1.
What information should I provide for a quotation?
Provide the required quantity, destination, requested date, and any project-list context for verification.