Product information
Overview
Applications
- Electrical energy measurement: Measures voltage, current, energy, frequency, active power, reactive power and power factor.
- Measured-value acquisition: Provides cyclic and acyclic measured-value access with fixed or freely definable measured value sets.
Key Features
- Energy measurement functions: Measures voltage, current, energy, frequency, power, active power, reactive power and power factor.
- Measurement performance: Uses TRMS measurement for voltage and current, with a 2 kHz measurement-acquisition bandwidth and 50 ms typical cycle time for all channels.
- Electrical input range: Supports measurable line voltage up to 480 V between line conductors and measurable relative AC current from 1 % to 100 % relative to the secondary rated current 5 A.
- Diagnostics and configuration: Provides diagnostic and limit value alarms, hardware interrupts for up to 16 freely selectable process values, channel diagnostics, and firmware updates.
- Installation and connection: Uses BU type D0 and BU20-P12+A0+0B for 2-wire connection, with any mounting position and a 20 mm x 73 mm x 58 mm module size.
Technical Summary
| Product type | AI Energy Meter 480VAC ST |
|---|---|
| Firmware version | V4.0 |
| Usable BaseUnit | BU type D0 |
| Supported power supply systems | TT, TN |
| Rated supply voltage | AC 100 – 277 V |
| Line frequency | 47 Hz to 63 Hz |
| Voltage measurement | Up to 480 V between line conductors |
| Current measurement | 1 % to 100 % relative to the secondary rated current 5 A |
| Measurement procedure | TRMS for voltage and current |
| Typical cycle time | 50 ms; consistent update of all measured and calculated values |
| Mounting position | any |
Frequently Asked Questions
What is the exact product type of 6ES7134-6PA20-0BD0?
It is an AI Energy Meter 480VAC ST analog input module for SIMATIC ET 200SP.
Which BaseUnit is usable with this module?
The usable BaseUnit is BU type D0. For 2-wire connection, the source lists BU type D0 and BU20-P12+A0+0B.
What supply voltage does the module use?
The rated supply voltage is AC 100 – 277 V, with a permissible range from 90 V to 293 V.
Which measurements does it support?
It supports voltage, current, energy, frequency, power, active power, reactive power and power factor measurement.
Can you quote this exact module for a project?
Send the required quantity, destination and project-list context for a model-specific quotation.