Product information
Overview
Key Features
- 8 RTD/TC analog inputs: Supports 8 analog inputs for resistance thermometers, thermocouples, voltage and resistance measurements with 2-wire connection.
- 16-bit measurement resolution: Provides up to 16 bit resolution including sign, with a typical constant measurement current of 2 mA for resistance-type transmitters.
- Channel diagnostics: Includes channel-by-channel wire-break and overflow/underflow diagnostics, group error, diagnostic alarms and supply-voltage monitoring.
- Flexible signal ranges: Supports configurable temperature measurement units °C/°F/K and scalable measuring ranges, including voltage ranges from -1 V to +1 V and thermocouple types B, C, E, J, K, L, N, R, S, T, U and TXK/TXK(L) to GOST.
- 24 V DC supply: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- BaseUnit and installation options: Suitable for BU type A0 and A1, with mechanical coding element Type A. Shielded cable length is up to 200 m, or 50 m with thermocouples.
Technical Summary
| Product type | AI 8xRTD/TC 2-wire HF |
|---|---|
| Analog inputs | 8 |
| Resolution | 16 bit including sign |
| Supply voltage | 24 V DC; permissible range 19.2 V to 28.8 V |
| Compatible BaseUnits | BU type A0, A1 |
| Input connection | 2-wire connection; three-wire and four-wire resistance measurement: No |
| Channel diagnostics | Wire break and overflow/underflow, channel by channel; group error: Yes |
| Operating temperature | Horizontal installation: -30 °C to 60 °C; vertical installation: -30 °C to 50 °C |
| Firmware version | V2.1 |
Frequently Asked Questions
What is Siemens 6ES7134-6JF00-0CA1?
It is a SIMATIC ET 200SP analog input module, AI 8xRTD/TC 2-wire HF, with 8 analog inputs and 16-bit resolution.
Which BaseUnits are suitable for this module?
The module is suitable for BU type A0 and A1 and uses a 2-wire connection.
What diagnostics does the module provide?
It provides channel-by-channel wire-break and overflow/underflow diagnostics, group error, diagnostic alarms and supply-voltage monitoring.
What installation temperature range is supported?
For horizontal installation, the ambient temperature range is -30 °C to 60 °C. For vertical installation, it is -30 °C to 50 °C.
Can you quote this exact module for a project?
Send the required quantity, destination and project-list context to request a model-specific quotation.