Product information
Overview
Applications
- Current measurement: Measures current signals from 2-wire and 4-wire transducers across the supported input ranges.
Key Features
- 8 analog current inputs: Has 8 single-ended analog inputs for current measurement, supporting 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA ranges.
- 2-wire and 4-wire connections: Supports current measurement with 2-wire and 4-wire transducers; 4-wire connection requires BU type A0, A1 + potential distributor module.
- 16-bit resolution: Provides up to 16 bit resolution with overrange, including sign where applicable.
- 24 V supply and encoder output: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. Encoder supply has short-circuit protection and a maximum total current of 0.7 A for all encoders/channels.
- Diagnostics and status indication: Has module diagnostics, diagnostic alarm, supply-voltage monitoring, wire-break detection at 4 mA to 20 mA, short-circuit detection, group error, and green/red DIAG LED indication.
- SIMATIC ET 200SP integration: Suitable for BU type A0 and A1, with automatic encoding and a Type A mechanical coding element. STEP 7 TIA Portal configuration is integrated from version TIA Portal V21.
Technical Summary
| Product type designation | AI 8xI 2-/4-wire BA |
|---|---|
| Analog inputs | 8; Single-ended |
| Input ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution with overrange | 16 bit |
| Rated supply voltage | 24 V DC |
| Supply voltage range | 19.2 V to 28.8 V DC |
| Encoder supply output current, max. | 0.7 A; total current of all encoders/channels |
| Cycle time (all channels), min. | 1 ms; per channel |
| Usable BaseUnits | BU type A0, A1 |
| Firmware version | V2.0.0 |
Frequently Asked Questions
What is Siemens 6ES7134-6GF00-0AA1?
It is a SIMATIC ET 200SP analog input module with 8 single-ended current inputs and 2-wire/4-wire transducer support.
Which input ranges does this module support?
It supports 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA input ranges.
Which BaseUnits can be used?
The module is suitable for BU type A0 and A1. A 4-wire connection requires BU type A0, A1 + potential distributor module.
What supply voltage does it require?
The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
What should be included in a quotation request?
Send the required quantity, destination, requested date, and any project-list context for verification.