Overview
Key Features
- Analog input capacity: 2 analog inputs, both supporting current measurement.
- Input ranges and resolution: Supports 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA input ranges, with up to 16 bit resolution including sign.
- Supply and encoder output: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. Encoder supply output is 50 mA max. total for both channels in two-wire mode.
- Conversion performance: Minimum cycle time for all channels is 500 μs. Conversion time is 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, or 500 μs without filter.
- Diagnostics and protection: Provides supply-voltage monitoring, wire-break diagnosis at 4 mA to 20 mA, encoder-supply short-circuit diagnosis, group error, overflow/underflow, and reverse-polarity protection.
- Installation and dimensions: Suitable for BU type A0, A1 and 1-wire, 2-wire, or 4-wire connections. Dimensions are 15 mm wide, 73 mm high, and 58 mm deep.
Technical Summary
| Product type designation | AI 2xI 2-/4-wire ST |
|---|---|
| Analog inputs | 2 |
| Input ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution with overrange | 16 bit including sign |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage range | 19.2 V to 28.8 V DC |
| Cycle time, all channels, min. | 500 μs |
| BaseUnits | BU type A0, A1 |
| Conversion time | 50 ms @ 60 Hz; 60 ms @ 50 Hz; 180 ms @ 16.6 Hz; 500 μs without filter |
| Diagnostics | Supply voltage, wire break at 4 mA to 20 mA, encoder-supply short-circuit, group error, overflow/underflow |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7134-6GB00-0BA1?
It is an AI 2xI 2-/4-wire ST SIMATIC ET 200SP analog input module.
Which BaseUnits and connection variants are supported?
It is suitable for BU type A0 and A1, with 1-wire, 2-wire, and 4-wire connections.
What supply voltage does the module require?
Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which diagnostics are available?
The module supports supply-voltage monitoring, wire-break diagnosis at 4 mA to 20 mA, encoder-supply short-circuit diagnosis, group error, and overflow/underflow.
What information should I provide for a quotation?
Provide the required quantity, destination, requested date, and any project list or configuration details for verification.