Product information
Overview
Key Features
- Relay output configuration: 3 digital relay outputs with isolated changeover contacts; current-sinking, current-sourcing, and parameterizable outputs are supported.
- Switching capacity: Maximum switching capacity is 5 A with a resistive load and 2 A with an inductive load.
- Supply and output voltage: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. Rated output voltage is 230 V AC.
- Diagnostics and substitute values: The module has supply-voltage monitoring, diagnostic alarms, module diagnostics, and connectable substitute values.
- BaseUnit and coding: Suitable BaseUnit: BU type U0. It has automatic encoding and a type C mechanical coding element; module color code is CC20.
- Installation-dependent current: For horizontal installation, maximum total output current is 15 A up to 50 °C and 12 A up to 60 °C. For vertical installation, it is 15 A up to 40 °C and 12 A up to 50 °C; maximum channel current is 4 A at the 12 A limits.
Technical Summary
| Product type | RQ 3x120VDC-230VAC/5A CO ST |
|---|---|
| Digital outputs | 3 relay outputs; changeover contact, isolated |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Rated output voltage | 230 V AC |
| Switching capacity | 5 A resistive load; 2 A inductive load, maximum |
| BaseUnit | BU type U0 |
| Module color code | CC20 |
| Firmware version | V0.0 |
| PROFINET GSDML | V2.34 |
| PROFIBUS GSD revisions | Revision 3 and 5 and higher |
| Product lifecycle | Active Product |
Frequently Asked Questions
What is the exact output configuration of the 6ES7132-6HC50-0BU0?
It has 3 digital relay outputs with isolated changeover contacts. The outputs are current-sinking, current-sourcing, and parameterizable.
What supply voltage does this relay module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
What BaseUnit is suitable for this module?
The suitable BaseUnit is BU type U0 for 2-wire and 3-wire connections.
Does the module include short-circuit protection?
It is without short-circuit protection. External protection for relay outputs is required with a miniature fuse of maximum 6.3 A tripping current, quick-response tripping characteristic, and 1 500 A breaking capacity.
What information should be included for a quotation?
Provide the required quantity, destination, requested date, and project list context for quotation review.