Product information
Overview
Applications
- Digital input control: The module supports controlling a digital input.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Key Features
- Digital output capacity: 4 parameterizable Triac digital outputs with current-sourcing operation; rated output current is 2 A per channel.
- Operating modes: Supports DQ, DQ with energy-saving function, phase control, half-wave, and full-wave operation. Phase control covers 8.5 … 100% of the phase angle.
- AC supply and output: Rated AC supply is 230 V at 47 … 63 Hz. Rated output voltage is 230 V for 24V AC to 230V AC.
- Output protection and diagnostics: Open-circuit detection is available channel by channel. Short-circuit and overload protection are not available; external fusing is necessary.
- BaseUnit and connection variants: Uses BU type U0 for 1-wire and 2-wire connections. A 3-wire connection uses BU type U0 + Potential distributor module.
- Engineering and diagnostics: Supports STEP 7 TIA Portal from V14, STEP 7 V5.5 or higher, PROFIBUS GSD as of Revision 5, and PROFINET GSDML V2.3. Channel, supply-voltage, and module diagnostics are available.
Technical Summary
| Product type | DQ 4×24 … 230 V AC/2 A HF |
|---|---|
| Digital outputs | 4 Triac outputs; current-sourcing: Yes; parameterizable: Yes |
| Rated supply | 230 V AC; 47 … 63 Hz |
| Output voltage | 230 V AC; 24V AC to 230V AC |
| Rated output current | 2 A per channel |
| Maximum module current | 8 A |
| BaseUnit | BU type U0 |
| Operating modes | DQ, DQ with energy-saving function, phase control, half-wave, full-wave |
| Phase control range | 8.5 … 100% of the phase angle |
| Color code | CC20 |
| Firmware update | Yes |
| Hardware functional status | From FS03 |
Frequently Asked Questions
What is the exact Siemens model and output type?
It is the Siemens 6ES7132-6FD00-0CU0 SIMATIC ET 200SP digital output module, type DQ 4×24 … 230 V AC/2 A HF, with 4 Triac outputs.
Which BaseUnit is used for this module?
BU type U0 is used for 1-wire and 2-wire connections. A 3-wire connection uses BU type U0 + Potential distributor module.
Does the module include short-circuit and overload protection?
It has no short-circuit protection and no overload protection. External fusing is necessary, and a miniature fuse must be provided in the module supply.
Which engineering versions and network descriptions are supported?
STEP 7 TIA Portal is configurable/integrated from V14, STEP 7 from V5.5 or higher, PROFIBUS from GSD Revision 5, and PROFINET from GSDML V2.3.
What quantity and destination should be included in a quotation request?
Include the required quantity, destination, and any project-list context when requesting a quotation.