Product information
Overview
Applications
- Controlling digital inputs: The digital outputs can control a digital input.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Key Features
- Digital output capacity: 16 parameterizable digital outputs with source output (PNP, current-sourcing); current-sinking is not supported.
- Output ratings: Rated output current is 0.5 A per signal and maximum current is 0.5 A per channel; maximum module current is 8 A.
- Supply and protection: Rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V and reverse polarity protection.
- Switching capacity: Maximum switching capacity is 0.5 A with resistive load and 5 W on lamp load; short-circuit protection is included.
- Diagnostics and status: The module has diagnostics, diagnostic alarms, supply-voltage monitoring, group error reporting, substitute values, a green PWR LED, and a green/red DIAG LED.
- BaseUnit and installation: Usable BaseUnit: BU type A0. For 2-wire, 3-wire, or 4-wire connections, BU type A0 plus a Potential distributor module is required.
Technical Summary
| Product type | DQ 16x24VDC/0.5A BA |
|---|---|
| Digital outputs | 16 |
| Output type | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V DC |
| Rated output current | 0.5 A per signal |
| Maximum module current | 8 A |
| Usable BaseUnit | BU type A0 |
| Firmware version | V0.0 |
| Hardware functional status | From FS03 |
| Protection and diagnostics | Short-circuit protection; module diagnostics; group error |
Frequently Asked Questions
What is the exact output configuration of Siemens 6ES7132-6BH00-0AA0?
It has 16 parameterizable source outputs (PNP, current-sourcing), with a rated output current of 0.5 A per signal.
Which BaseUnit is usable for this module?
The usable BaseUnit is BU type A0. For 2-wire, 3-wire, or 4-wire connections, BU type A0 plus a Potential distributor module is required.
What supply voltage does the module require?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which diagnostics are available?
The module supports diagnostics, diagnostic alarms, supply-voltage monitoring, group error reporting, substitute values, and module status indication through a green/red DIAG LED.
What information should be included for a quotation?
Provide the required quantity, destination, and project-list context for verification and quotation.