Product information
Overview
Key Features
- 4 digital outputs: The module has 4 parameterizable source outputs (PNP, current-sourcing) with a 2 A rated output current for signal "1".
- 24 V DC supply: Rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V and reverse polarity protection.
- Output protection: The outputs have electronic short-circuit protection and support output type according to IEC 61131, type 2.
- Channel diagnostics: Diagnostics include supply-voltage monitoring, channel-by-channel wire-break and short-circuit detection, group error indication, and diagnostic LEDs.
- ET 200SP configuration: The module is suitable for BU type A0, with automatic encoding and a Type A mechanical coding element.
- Isochronous mode: Isochronous mode is supported with 250 μs operation, a minimum bus cycle time of 500 μs, and maximum jitter of 8 μs.
Technical Summary
| Product type | DQ 4x DC 24 V/2 A HF |
|---|---|
| Number of digital outputs | 4 |
| Output type | Source output (PNP, current-sourcing) |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current | 2 A for signal "1" |
| Maximum current per module | 8 A |
| Short-circuit protection | Yes; Electronic |
| BaseUnit | BU type A0 |
| Firmware version | V2.0.3 |
| PROFINET GSDML | V2.3 |
| PROFIBUS GSD revision | GSD Revision 5 |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7132-6BD20-0CA0?
It is a SIMATIC ET 200SP digital output module with product type designation DQ 4x DC 24 V/2 A HF.
How many digital outputs does the module have?
It has 4 parameterizable source outputs. Current-sinking operation is not supported.
Which BaseUnit is supported?
The module is suitable for BU type A0. For 3-wire connection, BU type A0 with AUX terminals or a potential distributor module is specified; 4-wire connection requires BU type A0 plus a potential distributor module.
What diagnostics are available?
The module supports supply-voltage monitoring, channel-by-channel wire-break and short-circuit diagnostics, group error indication, and diagnostic alarm reporting.