Product information
Overview
Key Features
- 4 analog inputs: Supports 4 analog inputs for Pt 100, Pt 200, Pt 500, Pt 1000, Ni 100, Ni 200, Ni 500, Ni 1000 and resistor ranges from 0 to 3000 ohms.
- 24 V supply: Rated supply voltage is 24 V DC, with reverse polarity protection against destruction.
- Measurement performance: Cycle time for all channels is 83 ms at 50 Hz and 69 ms at 60 Hz. Resolution with overrange is 15 bit at 150, 300, 600 and 3 000 ohms; otherwise 15 bits + sign.
- Connection and cable limit: Supports two-wire, three-wire and four-wire resistance measurement. Shielded cable length is up to 30 m.
- Diagnostics and isolation: Provides channel diagnostics, diagnostic alarms, readable diagnostic information, wire-break and overflow/underflow detection. Analog inputs are isolated from the backplane bus but not between channels.
- Included and separate components: The bus module is included. Connection module IO 6ES7194-4..00-0AA0 is ordered separately.
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Module type | SIMATIC DP electronic module for ET 200 PRO, 4 AI RTD High Feature |
| Rated supply voltage | 24 V DC |
| Analog inputs | 4 |
| Supported resistance thermometers | Pt 100, Pt 200, Pt 500, Pt 1000, Ni 100, Ni 200, Ni 500, Ni 1000 |
| Cycle time (all channels) | 83 ms at 50 Hz; 69 ms at 60 Hz |
| Diagnostic functions | Channel diagnostics, diagnostic alarm, wire break, overflow/underflow |
Frequently Asked Questions
What is the exact module and input capacity?
It is Siemens 6ES7144-4JF00-0AB0, a SIMATIC DP electronic module for ET 200 PRO with 4 analog inputs.
Which resistance thermometers are supported?
The module supports Pt 100, Pt 200, Pt 500, Pt 1000, Ni 100, Ni 200, Ni 500 and Ni 1000.
What connection types are available for resistance measurement?
Two-wire, three-wire and four-wire resistance measurement are supported.
Is the connection module included?
The bus module is included. Connection module IO 6ES7194-4..00-0AA0 is ordered separately.
What details should be provided for a quotation?
Send the required quantity, destination and project-list context for an MRO or project quotation.