Product information
Overview
Key Features
- PROFINET IO Device interface: Supports PROFINET IO Device communication with 1 PROFINET interface and 2 switched ports.
- I/O module capacity: Supports up to 12 I/O modules without an additional power supply, or up to 30 I/O modules with an additional power supply.
- Supply voltage: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC.
- Isochronous operation: Supports isochronous mode with a 250 μs shortest clock pulse, 4 ms maximum cycle and 1 μs maximum jitter.
- Diagnostics and identification: Provides status, alarm and diagnostics functions, RUN, ERROR and MAINT LEDs, and I&M0 to I&M3 data.
- Engineering and firmware: Configurable with STEP 7 TIA Portal from V15; firmware version V4.1.0 and firmware updates are possible.
Technical Summary
| Product type | IM 155-5 PN ST |
|---|---|
| PROFINET interfaces | 1; 2 ports (switch) |
| PROFINET IO Device | Yes |
| Supply voltage, rated | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Modules per rack, max. | 30; I/O modules |
| Address space per station, max. | 512 byte; for input and output data respectively |
| Isochronous mode | Yes; shortest clock pulse 250 μs, maximum cycle 4 ms |
| PROFINET IRT | Yes; 250 μs to 4 ms in 125 μs frame |
| Firmware version | V4.1.0 |
| Product lifecycle | Active Product |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7155-5AA01-0AB0?
It has the product type designation IM 155-5 PN ST and is a PROFINET IO-DEVICE interface module for SIMATIC ET 200MP electronic modules.
How many I/O modules can this interface module support?
It supports up to 12 I/O modules without an additional power supply, or up to 30 I/O modules with an additional power supply.
What supply voltage does the module use?
The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.
Which PROFINET connections are provided?
It has 1 PROFINET interface with 2 switched ports and RJ45 Ethernet connections.
What should I include in a quotation request?