Product information
Overview
Key Features
- Four analog inputs: Has 4 analog inputs for voltage, resistance, resistance thermometer and thermocouple measurement.
- 24 V supply: Rated load voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC and reverse polarity protection against destruction.
- Measurement resolution and cycle time: Provides up to 16 bit resolution including sign. Minimum cycle time for all channels is 90 ms.
- M12 connections and protection: Has 4 M12 connections and IP65/67 degree of protection.
- Configurable engineering: Can be configured or integrated with STEP 7 V16 or higher, and with STEP 7 V5.5 SP4 and higher. PROFINET uses GSDML V2.34; PROFIBUS uses GSD as of Revision 5.
- Diagnostics and compensation: Supports parameterizable diagnostic and limit value alarms, wire-break diagnosis except for ±80 mV, overflow/underflow diagnosis, and parameterizable temperature compensation.
Technical Summary
| Product type | AI 4xRTD/TC |
|---|---|
| Analog inputs | 4 |
| Measurement types | Voltage, resistance, resistance thermometer and thermocouple |
| Rated load voltage | 24 V DC |
| Permissible load voltage | 20.4 V to 28.8 V DC |
| Resolution | Up to 16 bit including sign |
| Minimum cycle time | 90 ms for all channels |
| Connections | 4 M12 |
| Protection | IP65/67 |
| Firmware version | V2.0.x |
| HW functional status | FS03 |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7144-5KD50-0BA0?
It is a SIMATIC ET 200AL AI 4xRTD/TC analog input module with 4 M12 connections and IP67 protection.
What measurements does this module support?
It supports voltage, resistance, resistance thermometer and thermocouple measurement across 4 analog inputs.
What supply voltage does the module require?
The rated load voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.
Which engineering versions and network description files are supported?
It is configurable or integrable with STEP 7 V16 or higher and STEP 7 V5.5 SP4 and higher. PROFINET uses GSDML V2.34, while PROFIBUS uses GSD as of Revision 5.
Can you quote this module for a project requirement?
Please send the required quantity, destination and project list or requested date for model-specific quotation support.