PLC & Distributed I/O Parts

6ES7331-7KB02-0AB0

Product details

Product Code
6ES7331-7KB02-0AB0
Dimensions
15.1 × 12.8 × 5 cm
Weight
0.249 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Pricing, condition, availability and delivery terms are confirmed against the exact product reference.

Product information

Overview

Key Features

  • Isolated analog inputs: Has 2 analog inputs; the channels are not isolated from each other, but are isolated from the backplane bus.
  • Supported signal types: Supports voltage, current, thermocouple, resistance thermometer, and resistance inputs.
  • Resolution and conversion: Provides 9/12/14-bit unipolar or 9-bit + sign/12-bit + sign/14-bit + sign bipolar resolution; integration time is parameterizable at 2,5 / 16,67 / 20 / 100 ms.
  • Diagnostics and alarms: Has parameterizable diagnostics, diagnostic and limit value alarms, readable diagnostic information, and a red group error SF LED.
  • Signal connection: Supports voltage measurement, 2-wire and 4-wire current measurement, and two-wire, three-wire, and four-wire resistance measurement.
  • Installation and supply: Uses a required 20-pin front connector, supports removing/inserting with active backplane bus, and has a rated load voltage of 24 V DC with reverse polarity protection.

Technical Summary

Product 6ES7331-7KB02-0AB0
Product type SIMATIC S7-300 isolated analog input module
Analog inputs 2
Supported inputs Voltage, current, thermocouple, resistance thermometer, resistance
Resolution 9/12/14-bit unipolar; 9-bit + sign/12-bit + sign/14-bit + sign bipolar
Rated load voltage 24 V DC
Diagnostics Parameterizable diagnostics; diagnostic and limit value alarms
Front connector 20-pin
Lifecycle Product cancellation

Frequently Asked Questions

What signal types does 6ES7331-7KB02-0AB0 support?

It supports voltage, current, thermocouple, resistance thermometer, and resistance inputs.

How many analog inputs does this module have?

It has 2 analog inputs. The channels are not isolated from each other.

What connector is required?

A 20-pin front connector is required.

Does the module provide diagnostics and alarms?

Yes. It has parameterizable diagnostics, diagnostic and limit value alarms, readable diagnostic information, and a red group error SF LED.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote