Overview

Key Features

  • Digital outputs: Has 8 digital outputs with isolated channels and potential separation from the backplane bus through an optocoupler.
  • AC output current: Signal "1" output current is rated at 2 A; the permissible maximum is 2 A for 0 to 40 °C and 1 A for 40 to 60 °C.
  • Load voltage: Rated load voltage is 230 V; the stated AC range is 120/230 V AC, with a permissible range from 79 V to 264 V.
  • Diagnostics: Has parameterizable diagnostics and diagnostic alarms, with a red group error SF LED and green digital-output status indicators.
  • Connection and installation: Requires a 40-pin front connector. Dimensions are 40 mm width, 125 mm height and 120 mm depth; horizontal installation supports up to 8 A at 40 °C and 4 A at 60 °C.
  • Short-circuit protection: Short-circuit protection is available but must be provided externally with a 3.15 A / 250 V quick-response fuse.

Technical Summary

Product type SIMATIC S7-300 SM 322 digital output module
Digital outputs 8
Rated load voltage 230 V; 120/230 V AC
Output current, signal "1" 2 A rated; 10 mA to 2 A at 0 to 40 °C; 10 mA to 1 A at 40 to 60 °C
Required front connector 40-pin
Diagnostics Parameterizable diagnostics and diagnostic alarm
Product lifecycle Product cancellation

Frequently Asked Questions

What is the exact product type?

It is a Siemens SIMATIC S7-300 SM 322 digital output module, order number 6ES7322-5FF00-0AB0, with 8 isolated AC outputs.

What output current does the module support?

For signal "1", the rated output current is 2 A. The permissible range is 10 mA to 2 A at 0 to 40 °C and 10 mA to 1 A at 40 to 60 °C.

What connector is required?

The module requires a 40-pin front connector.

How is short-circuit protection configured?

Short-circuit protection must be provided externally with a 3.15 A / 250 V quick-response fuse.

What information should be included in a quotation request?

Include the required quantity, destination and project or MRO list context for model-specific quotation review.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote