PLC & Distributed I/O Parts

6ES7317-2AK14-0AB0

Product details

Product Code
6ES7317-2AK14-0AB0
Dimensions
15 × 12.8 × 5.2 cm
Weight
0.401 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Pricing, condition, availability and delivery terms are confirmed against the exact product reference.

Product information

Overview

Key Features

  • Central processing unit: CPU 317-2 DP with 1 024 kbyte integrated work memory and no work-memory expansion.
  • MPI/DP and PROFIBUS DP: Two integrated RS 485 interfaces support combined MPI / PROFIBUS DP and PROFIBUS DP, with transmission rates up to 12 Mbit/s.
  • PROFIBUS DP master capacity: The PROFIBUS DP master supports up to 124 DP devices and up to 8 devices activated or deactivated simultaneously.
  • Load memory and backup: Plug-in MMC load memory is supported up to 8 Mbyte. Backup is maintenance-free through the MMC and works without a battery for program and data.
  • Supply and installation data: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC. Dimensions are 40 mm × 125 mm × 130 mm and approximate weight is 360 g.

Technical Summary

Product type CPU 317-2 DP
Firmware version V3.3
Work memory 1 024 kbyte, not expandable
Interfaces 2 integrated RS 485 interfaces: combined MPI / PROFIBUS DP and PROFIBUS DP
Transmission rate 12 Mbit/s maximum for MPI and PROFIBUS DP
DP master capacity 124 DP devices maximum
Load memory Plug-in MMC, 8 Mbyte maximum
Supply voltage 24 V DC rated; 19.2 V to 28.8 V DC permissible range
Digital inputs / outputs 0 / 0
PROFINET interfaces 0

Frequently Asked Questions

What is the exact product type of Siemens 6ES7317-2AK14-0AB0?

It has the product type designation CPU 317-2 DP and is a SIMATIC S7-300 central processing unit.

What supply voltage does the CPU 317-2 DP require?

The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V DC.

Which interfaces and protocols are available?

It has 2 integrated RS 485 interfaces: combined MPI / PROFIBUS DP and PROFIBUS DP. MPI and PROFIBUS DP support transmission rates up to 12 Mbit/s; PROFIBUS DP supports master and device operation, with a DP slave at both interfaces simultaneously not possible.

Does the configuration include a Micro Memory Card?

It requires a Micro Memory Card; plug-in MMC load memory is supported up to 8 Mbyte.