- Module capacity: Supports up to 12 modules per DP device interface.
- PROFIBUS DP communication: Uses PROFIBUS DP to EN 50170 with transmission rates up to 12 Mbit/s and automatic baud rate search.
- Supply voltage: Rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V.
- Time stamping: Time-stamp accuracy is 1 ms at up to 8 modules and 10 ms at up to 12 modules; up to 128 digital inputs are stampable per station, with a maximum of 32 signals per slot.
- Connection and protection: The connection is a 9-pin sub D socket, and the degree of protection is IP20.
- Configuration software: Supports STEP 7, COM PROFIBUS, and non-Siemens tools via the GSD file SI05801E.GSG.
Technical Summary
| Product type designation | IM 153-2 DP HF |
|---|---|
| Module capacity | 12 modules per DP device interface, max. |
| Bus protocol | PROFIBUS DP to EN 50170 |
| Transmission rate | 12 Mbit/s, max. |
| Supply voltage | 24 V DC rated; 20.4 V to 28.8 V permissible range |
| Time-stamp accuracy | 1 ms at up to 8 modules; 10 ms at up to 12 modules |
| Stampable digital inputs | 128 signals/station, max.; 32 signals/slot, max. |
| Connection | 9-pin sub D socket |
| Configuration software | STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file |
| Protection | IP20 |
| Operating temperature | 0 °C to 60 °C; vertical installation 0 °C to 40 °C |
Frequently Asked Questions
Is 6ES7153-2BA10-0XB0 the IM 153-2 DP HF variant?
Yes. The product type designation is IM 153-2 DP HF.
What supply voltage does this module require?
The rated supply voltage is 24 V DC. The permissible range is 20.4 V to 28.8 V.
How many modules can be used with the DP device interface?
Up to 12 modules can be used per DP device interface.
Which connection and communication interface are provided?
The connection is a 9-pin sub D socket. Communication uses RS 485 with PROFIBUS DP to EN 50170, at up to 12 Mbit/s.
What information should be included for a quotation request?
Include the required quantity, destination, and project-list context for model-specific verification.