Product information

Overview

Key Features

  • 2 analog voltage outputs: The module has 2 analog outputs with voltage output short-circuit protection and a maximum short-circuit current of 25 mA.
  • Selectable voltage ranges: Supported output ranges are 1 V to 5 V and -10 V to +10 V.
  • Resolution per channel: Maximum resolution with overrange is 14 bit including sign; 1 V to 5 V: 12 bit, ±10 V: 13 bit + sign.
  • Fast cycle time: Cycle time for all channels is maximum 1.5 ms.
  • ET200S mechanical dimensions: Width: 15 mm; height: 81 mm; depth: 52 mm; weight, approx.: 40 g.
  • Connection and cable limits: Two-wire and four-wire voltage-output connections are supported. The two-wire connection is without compensation of the line resistances; shielded cable length is maximum 200 m.

Technical Summary

Product type SIMATIC DP electronics module for ET200S
Product lifecycle Product cancellation
Analog outputs 2
Output ranges 1 V to 5 V; -10 V to +10 V
Resolution with overrange 14 bit including sign; 1 V to 5 V: 12 bit, ±10 V: 13 bit + sign
Cycle time All channels, max. 1.5 ms
Load voltage L+ 24 V DC, rated value; from power module
Load impedance Voltage outputs, min. 1 kΩ; capacitive load, max. 1 μF
Short-circuit protection Yes; maximum short-circuit current 25 mA

Frequently Asked Questions

What is the exact product identified here?

It is Siemens 6ES7135-4FB01-0AB0, a SIMATIC DP electronics module for ET200S.

How many analog outputs does the module have?

It has 2 analog voltage outputs.

Which output ranges are supported?

It supports 1 V to 5 V and -10 V to +10 V.

What connection options are available?

Two-wire and four-wire voltage-output connections are supported. The two-wire connection is without compensation of the line resistances.

What should be included in a quotation request?

Include the required quantity and destination for model-specific quotation support.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote