Product information
Overview
Applications
- RTD temperature measurement: The module supports temperature measurement using Pt100 and Ni100 resistance thermometers.
- Resistance measurement: The module supports resistance measurement using 0 to 150 ohms, 0 to 300 ohms and 0 to 600 ohms input ranges.
Key Features
- RTD and resistance inputs: 4 analog inputs support Pt100 and Ni100 resistance thermometers plus 0 to 150 ohms, 0 to 300 ohms and 0 to 600 ohms ranges.
- Flexible sensor connections: Resistance measurement supports two-wire, three-wire and four-wire signal-encoder connections.
- Measurement resolution: Resolution with overrange is up to 16 bit including sign; 150 ohms provides 14 bit, while 300 ohms and 600 ohms provide 15 bit.
- Supply and diagnostics: The module has a rated load voltage of 24 V DC from the power module, reverse polarity protection, wire-break and group-error diagnostics, and a red group-error SF LED.
- Electrical isolation: The analog inputs are isolated from the backplane bus and load voltage L+, but not from one another.
- Mechanical dimensions: The module has a width of 15 mm, height of 81 mm, depth of 52 mm and approximate weight of 40 g.
Technical Summary
| Product type | SIMATIC DP electronics module for ET 200S |
|---|---|
| Analog inputs | 4; 2 for 3 or 4-wire connection |
| Supported sensors | Pt100, Ni100 |
| Supported resistance ranges | 0 to 150 ohms; 0 to 300 ohms; 0 to 600 ohms |
| Rated load voltage | 24 V DC; from power module |
| Resolution with overrange | 16 bit including sign; 150 ohms: 14 bit; 300, 600 ohms: 15 bit; Pt100, Ni100: 16 bit |
| Conversion time per channel | 66 / 80 ms; additional conversion time for diagnostic wire break test |
| Protection and diagnostics | Reverse polarity protection; short-circuit-proof transmitter supply; wire break, group error and overflow/underflow diagnostics |
Frequently Asked Questions
What exact Siemens module is this?
It is the 6ES7134-4JB51-0AB0 SIMATIC DP electronics module for ET 200S.
Which sensors and resistance ranges does it support?
It supports Pt100 and Ni100 resistance thermometers, plus 0 to 150 ohms, 0 to 300 ohms and 0 to 600 ohms input ranges.
What connection types are supported for resistance measurement?
Two-wire, three-wire and four-wire signal-encoder connections are supported.
Can you quote this module for my requirement?
Send the required quantity, destination and project-list context for a model-specific quotation.