- Analog input capacity: 4 analog inputs support a 4 mA to 20 mA current range into 25 Ohm.
- Resolution and cycle time: Resolution with overrange is 13 bit including sign; the maximum cycle time for all channels is 40 ms (33 to 40 ms).
- 2-wire transmitter supply: Power supply to the transmitters is present and short-circuit proof, at approximately 200 mA for the module.
- Rated load voltage: Rated load voltage L+ is 24 V DC from the power module, with reverse polarity protection.
- Diagnostics: Diagnostics include wire break for the 1 to 5 V measuring range only, group error, and overflow/underflow; a red SF LED indicates group error.
- Mechanical configuration: The module has a 15 mm width, 81 mm height, 52 mm depth, and approximate weight of 40 g.
Technical Summary
| Product type | SIMATIC DP electronics module ET 200S 4AI standard I-2-wire |
|---|---|
| Analog inputs | 4 |
| Input range | 4 mA to 20 mA; into 25 Ohm |
| Resolution with overrange | 13 bit including sign |
| Cycle time, all channels, max. | 40 ms; 33 to 40 ms |
| Rated load voltage L+ | 24 V DC; from power module |
| Transmitter supply | Present; short-circuit proof, approx. 200 mA for module |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is the exact function and signal type of 6ES7134-4GD00-0AB0?
It is a SIMATIC DP ET 200S 4AI standard I-2-wire electronics module for 4 analog current inputs using 4 mA to 20 mA signals.
What are the input resolution and maximum cycle time?
Resolution with overrange is 13 bit including sign. The maximum cycle time for all channels is 40 ms (33 to 40 ms).
What supply does the module use?
The rated load voltage L+ is 24 V DC from the power module. Reverse polarity protection is provided.
What diagnostics are supported?
The module supports wire-break diagnostics for the 1 to 5 V measuring range only, group error, and overflow/underflow. Group error is indicated by a red SF LED.
How can I request a quotation for this configuration?