PLC & Distributed I/O Parts

6ES7134-4GD00-0AB0

Product details

Product Code
6ES7134-4GD00-0AB0
Dimensions
9.1 × 6.2 × 2.2 cm
Weight
0.045 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Pricing, condition, availability and delivery terms are confirmed against the exact product reference.

Product information

Overview

Key Features

  • Analog input capacity: 4 analog inputs support a 4 mA to 20 mA current range into 25 Ohm.
  • Resolution and cycle time: Resolution with overrange is 13 bit including sign; the maximum cycle time for all channels is 40 ms (33 to 40 ms).
  • 2-wire transmitter supply: Power supply to the transmitters is present and short-circuit proof, at approximately 200 mA for the module.
  • Rated load voltage: Rated load voltage L+ is 24 V DC from the power module, with reverse polarity protection.
  • Diagnostics: Diagnostics include wire break for the 1 to 5 V measuring range only, group error, and overflow/underflow; a red SF LED indicates group error.
  • Mechanical configuration: The module has a 15 mm width, 81 mm height, 52 mm depth, and approximate weight of 40 g.

Technical Summary

Product type SIMATIC DP electronics module ET 200S 4AI standard I-2-wire
Analog inputs 4
Input range 4 mA to 20 mA; into 25 Ohm
Resolution with overrange 13 bit including sign
Cycle time, all channels, max. 40 ms; 33 to 40 ms
Rated load voltage L+ 24 V DC; from power module
Transmitter supply Present; short-circuit proof, approx. 200 mA for module
Product lifecycle Product cancellation

Frequently Asked Questions

What is the exact function and signal type of 6ES7134-4GD00-0AB0?

It is a SIMATIC DP ET 200S 4AI standard I-2-wire electronics module for 4 analog current inputs using 4 mA to 20 mA signals.

What are the input resolution and maximum cycle time?

Resolution with overrange is 13 bit including sign. The maximum cycle time for all channels is 40 ms (33 to 40 ms).

What supply does the module use?

The rated load voltage L+ is 24 V DC from the power module. Reverse polarity protection is provided.

What diagnostics are supported?

The module supports wire-break diagnostics for the 1 to 5 V measuring range only, group error, and overflow/underflow. Group error is indicated by a red SF LED.

How can I request a quotation for this configuration?

Send the required quantity, destination, and project or MRO context for quotation review.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry