Product information
Overview
Key Features
- High and low overload output ratings: Rated output power is 55.00 kW | 75.00 hp for HO and 75.00 kW | 100.00 hp for LO. HO supports 200% for 3 s, 150% for 57 s and 100% for 240 s at -20 … 50 °C; LO supports 150% for 3 s, 110% for 57 s and 100% for 240 s at -20 … 40 °C.
- Input and output ratings: Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz. Output: 3 AC, 400V IEC | 480V NEC 1), with maximum output current of 220.00 A.
- Built-in braking chopper: The power module has a built-in braking chopper and a DC link with screw-type terminals for a braking resistor.
- Control performance: Output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control. Pulse frequency is 2 kHz.
- Connections and motor cable length: Line-side and motor-end connections use M10 bolts for 35.00 … 120.00 mm2 conductors. Maximum motor cable length is 300 m (984.25 ft) shielded or 450 m (1,476.38 ft) unshielded.
- Mechanical configuration and protection: Frame size: FSF. Dimensions are 708 mm high × 305 mm wide × 357 mm deep. Protection: IP20 / UL open type. The unit is without a filter, control unit and panel.
Technical Summary
| Product | 6SL3210-1PE31-5UL0 |
|---|---|
| Product type | SINAMICS G120 POWER MODULE PM240-2 |
| Input | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Rated output power (HO) | 55.00 kW | 75.00 hp |
| Rated output power (LO) | 75.00 kW | 100.00 hp |
| Maximum output current | 220.00 A |
| Output frequency | 0 … 200 Hz vector control; 0 … 550 Hz V/f control |
| Braking | Built-in braking chopper |
| Frame size | FSF |
| Protection | IP20 / UL open type |
| Exclusions | Without filter, control unit and panel |
Frequently Asked Questions
What is the exact Siemens model and product type?
The exact model is Siemens 6SL3210-1PE31-5UL0, a SINAMICS G120 POWER MODULE PM240-2.
What are the HO and LO output ratings?
HO rated output power is 55.00 kW | 75.00 hp, with 200% for 3 s, 150% for 57 s and 100% for 240 s at -20 … 50 °C. LO rated output power is 75.00 kW | 100.00 hp, with 150% for 3 s, 110% for 57 s and 100% for 240 s at -20 … 40 °C.
Which control frequency ranges are supported?
The output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
What connections and motor cable lengths are provided?
Line-side and motor-end connections use M10 bolts with 35.00 … 120.00 mm2 conductors. Maximum motor cable length is 300 m (984.25 ft) shielded or 450 m (1,476.38 ft) unshielded.
What is included in this configuration?
It is without a filter, control unit and panel. For a quotation, provide the required quantity, destination and requested date.