Overview
Key Features
- Power module configuration: SINAMICS Power Module PM240-2 with integrated Class A filter and integrated braking chopper.
- Supply: 380-480 V 3 AC +10/-10%, 47-63 Hz.
- High-overload rating: 5.5 kW at 200% for 3 s, 150% for 57 s and 100% for 240 s; ambient temperature -10 to +50 °C.
- Low-overload rating: 7.5 kW at 150% for 3 s, 110% for 57 s and 100% for 240 s; ambient temperature -10 to +40 °C.
- Mechanical configuration: FSB, 345 x 154 x 171 mm (H x W x D).
- Protection and exclusions: Degree of protection IP20-PT. Without Control Unit and operation panel.
Technical Summary
| Product type | SINAMICS Power Module PM240-2 |
|---|---|
| Supply | 380-480 V 3 AC +10/-10%, 47-63 Hz |
| High-overload power | 5.5 kW at 200% 3 s, 150% 57 s, 100% 240 s; ambient temperature -10 to +50 °C |
| Low-overload power | 7.5 kW at 150% 3 s, 110% 57 s, 100% 240 s; ambient temperature -10 to +40 °C |
| Integrated features | Class A filter and braking chopper |
| Mechanical size | 345 x 154 x 171 mm (H x W x D) |
| Frame size | FSB |
| Degree of protection | IP20-PT |
| Configuration exclusions | Without Control Unit and operation panel |
| Firmware release | Released as of CU firmware version V4.6 |
| Product lifecycle | Product cancellation |
Frequently Asked Questions
What is the configuration of Siemens 6SL3211-1PE21-8AL0?
It is a SINAMICS Power Module PM240-2 with an integrated Class A filter and braking chopper.
What are the high- and low-overload ratings?
High overload is 5.5 kW at 200% for 3 s, 150% for 57 s and 100% for 240 s at -10 to +50 °C. Low overload is 7.5 kW at 150% for 3 s, 110% for 57 s and 100% for 240 s at -10 to +40 °C.
What are the mounting dimensions and protection rating?
The FSB module measures 345 x 154 x 171 mm (H x W x D) and has degree of protection IP20-PT.
Does the configuration include a Control Unit and operation panel?
It is without Control Unit and operation panel.
What information should be included in a quotation request?
Include the required quantity and destination for model-specific verification and quotation.