Product information
Overview
Key Features
- Current and power ratings: Rated operational current is 551 A at 40 °C, 494 A at 50 °C, and 438 A at 60 °C. At 400 V, the rated power is 315 kW in the standard circuit and 560 kW in the inside-delta circuit.
- Inside-delta performance: The inside-delta circuit has rated operational current of 954 A at 40 °C, 856 A at 50 °C, and 759 A at 60 °C, with a minimum load of 8%.
- Motor and device protection: The soft starter has intrinsic device protection, motor overload protection, thermistor motor protection evaluation, adjustable current limitation, and external reset.
- Control supply and connections: The control supply is AC, with a rated voltage of 230 V at 50 Hz and 60 Hz. The main current circuit uses busbar connections; auxiliary and control circuits use screw-type terminals.
- Mechanical installation: Dimensions are 510 mm wide, 640 mm high, and 290 mm deep. Mounting uses screw fixing; the vertical mounting surface is rotatable by +/-90° and tiltable by +/-22.5° to the front and back.
Technical Summary
| Product type | SIRIUS soft starter |
|---|---|
| Rated operational current at 40 °C, standard circuit | 551 A |
| Rated power at 400 V, standard circuit | 315 kW |
| Rated power at 400 V, inside-delta circuit | 560 kW |
| Operating voltage, standard and inside-delta circuit | 200 … 460 V |
| Control supply | 230 V AC at 50 Hz and 60 Hz |
| Main current connection | Busbar connection |
| Auxiliary and control connection | Screw-type terminals |
| Mounting | Screw fixing; vertical mounting surface, +/-90° rotatable and +/-22.5° tiltable |
| Front protection class | IP00 |
| Product lifecycle | Start of final year of support |
Frequently Asked Questions
What are the 400 V ratings for the 3RW4453-6BC44?
At 400 V, the rated power is 315 kW in the standard circuit and 560 kW in the inside-delta circuit. The rated operational current at 40 °C is 551 A in the standard circuit and 954 A in the inside-delta circuit.
What control supply and connections does this soft starter have?
It has a 230 V AC control supply at 50 Hz and 60 Hz. The main current circuit uses busbar connections, while auxiliary and control circuits use screw-type terminals.
How is the 3RW4453-6BC44 mounted?
It uses screw fixing. With a vertical mounting surface, it is rotatable by +/-90° and tiltable by +/-22.5° to the front and back.
Is this configuration a current product?
It is a phased-out product at the start of its final year of support. The collected description identifies SIRIUS 3RW5 as the successor and >>3RW5548-6HA14<< as the preferred successor type.