- Rated current and power: Rated operational current: 38 A at 40 °C. Standard circuit power: 18.5 kW at 400 V and 22 kW at 500 V, both at 40 °C.
- Operating voltage and frequency: Operating voltage at standard circuit: 400 … 600 V, with -15 % relative negative tolerance and 10 % relative positive tolerance. Rated operating frequency: 50 … 60 Hz.
- Control supply: Control supply voltage: 110 … 230 V AC at 50 Hz or 60 Hz, and 110 … 230 V DC. Control supply voltage type: AC/DC.
- Protection and functions: Has an integrated bypass contact system, thyristors, intrinsic device protection, motor overload protection, external reset and adjustable current limitation. Evaluation of thermistor motor protection, inside-delta circuit and motor brake output are not included.
- Installation and connections: S0 device with screw and snap-on mounting, 45 mm width, 125 mm height and 155 mm depth. Main, auxiliary and control circuits use screw-type terminals; the front has IP20 protection according to IEC 60529.
Technical Summary
| Product designation | Soft starter |
|---|---|
| Rated operational current | 38 A at 40 °C |
| Standard circuit power | 18.5 kW at 400 V; 22 kW at 500 V, both at 40 °C |
| Operating voltage | 400 … 600 V at standard circuit |
| Operating frequency | 50 … 60 Hz |
| Control supply | 110 … 230 V AC/DC |
| Device size | S0 |
| Mounting | Screw and snap-on mounting |
| Connections | Screw-type terminals |
| Front protection | IP20 according to IEC 60529 |
| Operating ambient temperature | -25 … +60 °C |
Frequently Asked Questions
What is the rated current of Siemens 3RW4028-1BB15?
The rated operational current is 38 A at 40 °C, 34 A at 50 °C and 31 A at 60 °C.
What supply voltage does this soft starter use?
The operating voltage at standard circuit is 400 … 600 V. The control supply is 110 … 230 V AC at 50 Hz or 60 Hz, or 110 … 230 V DC.
How is the 3RW4028-1BB15 mounted and connected?
It uses screw and snap-on mounting. The main, auxiliary and control circuits use screw-type terminals.
Which protection functions are included?
It has intrinsic device protection, motor overload protection, external reset and adjustable current limitation. It does not include evaluation of thermistor motor protection.