Product information
Overview
Key Features
- Rated input: 3 AC input, 380 … 480 V +10 % -20 %, with 47 … 63 Hz line frequency.
- Output ratings: Rated output power is 0.75 kW | 1.00 hp for low overload and 0.55 kW | 0.75 hp for high overload.
- Overload capacity: Low overload: 150% for 3s, 110% for 57s and 100% for 240s. High overload: 200% for 3s, 150% for 57s and 100% for 240s.
- I/O interface: The interface has 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog/digital input and 1 non-isolated analog output.
- Control and communication: Supported control includes V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control. Communication: USS/MODBUS RTU.
- Protection and connections: Protection is IP20 / UL open type. Line-side, motor-end and DC-link connections use plug-in screw terminals; the integrated filter is Class A.
Technical Summary
| Product | Siemens 6SL3210-1KE12-3AB2 SINAMICS G120C |
|---|---|
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated output power (LO) | 0.75 kW | 1.00 hp |
| Rated output power (HO) | 0.55 kW | 0.75 hp |
| Max. output current | 3.40 A |
| Output frequency for vector control | 0 … 240 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| I/O interface | 6DI, 2DO, 1AI, 1AO, 1 fail-safe digital input |
| Communication | USS/MODBUS RTU |
| Protection | IP20 / UL open type |
| Frame size | FSAA |
Frequently Asked Questions
What is the exact Siemens model and converter type?
It is the Siemens 6SL3210-1KE12-3AB2 SINAMICS G120C compact converter.
What are the low-overload and high-overload output ratings?
Low overload is 0.75 kW | 1.00 hp; high overload is 0.55 kW | 0.75 hp. The overload durations are 150% for 3s, 110% for 57s and 100% for 240s at low overload, and 200% for 3s, 150% for 57s and 100% for 240s at high overload.
Which communication interface and I/O are provided?
Communication is USS/MODBUS RTU. The I/O includes 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog/digital input and 1 non-isolated analog output.
What protection and connections does the configuration have?
Protection is IP20 / UL open type. Line-side, motor-end and DC-link connections use plug-in screw terminals.