Overview

Key Features

  • Rated power and overload: Rated power is 4.00 kW | 5.00 hp for low overload and 3.00 kW | 4.00 hp for high overload. Low overload supports 150% for 3s, 110% for 57s and 100% for 240s; high overload supports 200% for 3s, 150% for 57s and 100% for 240s.
  • Input and output ratings: Input and output each have 3 AC phases. Input line voltage is 380 … 480 V +10 % -20 % at 47 … 63 Hz.
  • Control and communication: Supported control includes V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control. Communication: PROFIBUS DP.
  • I/O configuration: The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog/digital input with 10 bit resolution, and 1 non-isolated analog output.
  • Connections and protection: Line-side, motor-end and DC-link connections use plug-in screw terminals. Protection is IP20 / UL open type; frame size is FSA.

Technical Summary

Product 6SL3210-1KE18-8AP1
Product family SINAMICS G120C
Input line voltage 380 … 480 V +10 % -20 %
Line frequency 47 … 63 Hz
Rated power (LO) 4.00 kW | 5.00 hp
Rated power (HO) 3.00 kW | 4.00 hp
Communication PROFIBUS DP
Digital inputs 6 standard digital inputs; 1 fail-safe digital input
Analog/digital input 1 differential input, 10 bit resolution
Protection IP20 / UL open type
Frame size FSA

Frequently Asked Questions

What is the exact product identification?

It is Siemens 6SL3210-1KE18-8AP1 from the SINAMICS G120C family.

What are the low-overload and high-overload power ratings?

Low-overload rated power is 4.00 kW | 5.00 hp; high-overload rated power is 3.00 kW | 4.00 hp.

Which communication interface and I/O are included?

It has PROFIBUS DP, 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog/digital input, and 1 non-isolated analog output.

What protection and mounting dimensions are specified?

Protection is IP20 / UL open type. Frame size is FSA; dimensions are 73 mm width and 203 mm depth.

What information should I provide for a quotation?

Provide the required quantity, destination and requested date for quotation review.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote