Product information
Overview
Key Features
- Power ratings: Rated output power: 15.00 kW | 20.00 hp (LO) and 11.00 kW | 15.00 hp (HO).
- Input supply: Input: 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz.
- Overload performance: High overload: 11 kW at 200% for 3s, 150% for 57s, and 100% for 240 s at 0 … 50 °C. Low overload: 15 kW at 150% for 3s, 110% for 57s, and 100% for 240 s at 0 … 40 °C.
- Control frequency ranges: Output frequency: 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control; pulse frequency: 4 kHz.
- Connections and motor cable: Screw-type terminals on the line side and motor end accept 2.50 … 10.00 mm2 (AWG 14 … AWG 8). Maximum motor cable length: 25 m (82.02 ft) shielded or 100 m (328.08 ft) unshielded.
- Mechanical protection: Frame size FSC; degree of protection IP20 / UL open type. Dimensions: 189 mm width, 334 mm height, and 185 mm depth; net weight: 7.50 kg (16.53 lb).
Technical Summary
| Product | SINAMICS G120 Power Module PM 250 |
|---|---|
| Order number | 6SL3225-0BE31-1AA1 |
| Product lifecycle | Active Product |
| Input supply | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Rated output power (LO) | 15.00 kW | 20.00 hp |
| Rated output power (HO) | 11.00 kW | 15.00 hp |
| Output frequency for vector control | 0 … 200 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Filter class (integrated) | Class A |
| Frame size | FSC |
| Degree of protection | IP20 / UL open type |
Frequently Asked Questions
What is the exact product type and order number?
It is a SINAMICS G120 Power Module PM 250 with order number 6SL3225-0BE31-1AA1.
What are the low-overload and high-overload power ratings?
Low-overload rated power is 15.00 kW | 20.00 hp; high-overload rated power is 11.00 kW | 15.00 hp.
What control frequency ranges does it support?
Output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control.
What protection and mechanical configuration does it have?
It has IP20 / UL open type protection and FSC frame size. It is without Control Unit and BOP.
What information should be included for a quotation request?
Include the required quantity, destination, and requested date for MRO or project quotation review.