Product information
Overview
Key Features
- Rated input: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Rated current: 9.50 A (LO) and 8.20 A (HO).
- Output ratings: Rated power: 3.00 kW | 4.00 hp (LO) and 2.20 kW | 3.00 hp (HO). Rated current: 7.30 A (LO) and 5.60 A (HO).
- Overload capacity: Low overload: 3.00 kW at 150% for 3s, 110% for 57s and 100% for 240s. High overload: 2.20 kW at 200% for 3s, 150% for 57s and 100% for 240s.
- Control and interfaces: The converter has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, 1 non-isolated analog output and PROFIBUS DP.
- Protection and filter: Protection: IP20 / UL open type. Integrated filter: Class A. Safe Torque Off is integrated.
- Mechanical configuration: Frame size: FSA. Dimensions: 73 mm (2.87 in) width and 203 mm (7.99 in) depth. Net weight: 1.70 kg (3.75 lb).
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Input voltage | 380 … 480 V +10 % -20 % |
| Input frequency | 47 … 63 Hz |
| Rated power (LO) | 3.00 kW | 4.00 hp |
| Rated power (HO) | 2.20 kW | 3.00 hp |
| Communication | PROFIBUS DP |
| Protection | IP20 / UL open type |
| Frame size | FSA |
| Integrated filter | Class A |
| Safe Torque Off | Integrated |
Frequently Asked Questions
What are the low-overload and high-overload ratings?
Low overload is 3.00 kW at 150% for 3s, 110% for 57s and 100% for 240s. High overload is 2.20 kW at 200% for 3s, 150% for 57s and 100% for 240s.
Which communication interface and I/O are included?
The converter has PROFIBUS DP, 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input and 1 non-isolated analog output.
What are the mounting dimensions and protection?
Frame size is FSA. Width is 73 mm (2.87 in), depth is 203 mm (7.99 in), and protection is IP20 / UL open type.
What quantity and destination should be included in a quotation request?
Please provide the required quantity and destination for a model-specific quotation.