Product information
Overview
Key Features
- Rated input and output: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, 0.55 kW at low overload or 0.37 kW at high overload.
- Overload performance: Low overload: 150% for 3s, 110% for 57s, 100% for 240s. High overload: 200% for 3s, 150% for 57s, 100% for 240s.
- Control and frequency ranges: Supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control. Output frequency is 0 … 240 Hz for vector control and 0 … 550 Hz for V/f control.
- I/O and safety interface: Unfiltered external 24V I/O interface with 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output. Safe Torque Off is integrated.
- Fieldbus and connections: Fieldbus: PROFIBUS-DP. Line-side, motor-end, and DC-link connections use plug-in screw terminals; the DC link supports a maximum line length of 15 m (49.21 ft).
- Mechanical protection and cooling: Frame size: FSAA. Degree of protection: IP20 / UL open type. Air cooling uses an integrated fan; dimensions are 173 x 73 x 155 mm (H x W x D).
Technical Summary
| Product type | SINAMICS G120C compact converter |
|---|---|
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated output power (LO) | 0.55 kW | 0.75 hp |
| Rated output power (HO) | 0.37 kW | 0.50 hp |
| Fieldbus | PROFIBUS-DP |
| I/O | 6DI, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, 1 non-isolated analog output |
| Control modes | V/f linear / square-law / parameterizable; V/f with flux current control (FCC); V/f ECO linear / square-law; sensorless vector control |
| Protection | IP20 / UL open type |
Frequently Asked Questions
What input supply does Siemens 6SL3210-1KE11-8UP2 use?
It uses 3 AC input at 380 … 480 V +10 % -20 % and 47 … 63 Hz.
What output power is supported under low and high overload?
Rated output power is 0.55 kW | 0.75 hp under low overload and 0.37 kW | 0.50 hp under high overload.
Which fieldbus and I/O interfaces are included?
It includes PROFIBUS-DP, 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output.
What protection and mechanical configuration does it have?
It has IP20 / UL open type protection, FSAA frame size, and dimensions of 173 x 73 x 155 mm (H x W x D).
What information should be included in a quotation request?
Include the required quantity, destination, requested date, and any project list or technical verification requirements.