Product information
Overview
Key Features
- Relay output configuration: 1 relay output with 2 NO contacts; digital output type: Relays.
- Switching capacity: Maximum 5 A with resistive load, 25 W with lamp load, and 2 Hz with resistive load.
- Supply and load voltage: Rated supply voltage: 24 V DC; load voltage: 24 V DC and 24 … 230 V AC.
- Output current by installation conditions: For horizontal installation: maximum 5 A up to 40 °C, 4 A up to 50 °C, and 3 A up to 60 °C. For vertical installation: maximum 3 A up to 50 °C; see manual derating data.
- Diagnostics and status: Diagnostics function, green/red DIAG LED, and green channel status LED.
- Isolation and protection: Potential separation between channels, backplane bus, and electronics supply; 250 V AC between channels and backplane bus/supply voltage with reinforced insulation.
Technical Summary
| Product type | F-RQ 24 … 48VDC/24 … 230VAC/5A ST |
|---|---|
| Digital outputs | 1 relay output; 2 NO contacts |
| Rated coil voltage | 24 V DC |
| Load voltage | 24 V DC and 24 … 230 V AC |
| Switching capacity, resistive load, max. | 5 A |
| Supply voltage range | 20.4 V to 28.8 V DC |
| BaseUnit | BU type F0 |
| Engineering | STEP 7 TIA Portal from V13; STEP 7 from V5.5 SP4 and higher |
| PROFINET GSD version | V2.31 |
| Permissible potential difference | 250 V AC (reinforced insulation) |
Frequently Asked Questions
What is the exact product type of Siemens 6ES7136-6RA00-0BF0?
It is an F-RQ 24 … 48VDC/24 … 230VAC/5A ST SIMATIC ET 200SP relay output module.
How many relay outputs and contacts does the module have?
It has 1 relay output with 2 NO contacts.
What supply and load voltages does it support?
The rated coil supply is 24 V DC. The load voltage is 24 V DC and 24 … 230 V AC.
What output current is permitted for installation conditions?
For horizontal installation, the maximum total output current is 5 A up to 40 °C, 4 A up to 50 °C, and 3 A up to 60 °C. For vertical installation, it is 3 A up to 50 °C; see the manual for derating data.
What information should I provide for a quotation?
Provide the required quantity, destination, requested date, and any project list or verification requirements.