Product information
Overview
Key Features
- Power and overload ratings: Rated power is 37.00 kW | 50.00 hp for HO and 45.00 kW | 60.00 hp for LO. High overload supports 200% for 3 s, 150% for 57 s, and 100% for 240 s at 0 … 50 °C ambient temperature; light overload supports 150% for 3 s, 110% for 57 s, and 100% for 240 s at 0 … 40 °C ambient temperature.
- Input and output: Input and output each use 3 AC phases. Input voltage is 380 … 480 V ±10 % at 47 … 63 Hz; output rated voltage is 400V IEC | 480V NEC.
- Control frequency ranges: Output frequency is 0 … 200 Hz for vector control and 0 … 550 Hz for V/f control. Pulse frequency is 4 kHz.
- Connections and motor cable: Line-side and motor-end connections use M6 bolts with 10.00 … 50.00 mm2 (AWG 8 … AWG 1) conductor cross-section. Maximum motor cable length is 50 m (164.04 ft) shielded or 100 m (328.08 ft) unshielded.
- Mechanical configuration: Frame size is FSE. Dimensions are 635 mm height, 275 mm width, and 204 mm depth; net weight is 21.00 kg (46.30 lb).
- Protection and included configuration: Degree of protection is IP20 / UL open type, with an integrated Class A filter and regeneration capability. The configuration is without a control unit and BOP.
Technical Summary
| Product | 6SL3225-0BE33-7AA0 |
|---|---|
| Product family | SINAMICS G120 PM250 |
| Lifecycle | Active Product |
| Rated power (HO) | 37.00 kW | 50.00 hp |
| Rated power (LO) | 45.00 kW | 60.00 hp |
| Input | 3 AC, 380 … 480 V ±10 %, 47 … 63 Hz |
| Output rated voltage | 400V IEC | 480V NEC |
| Output frequency for vector control | 0 … 200 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Degree of protection | IP20 / UL open type |
| Frame size | FSE |
Frequently Asked Questions
What is the rated power of Siemens 6SL3225-0BE33-7AA0?
Rated power is 37.00 kW | 50.00 hp for HO and 45.00 kW | 60.00 hp for LO.
What input supply does this power module use?
It uses 3 AC input at 380 … 480 V ±10 % and 47 … 63 Hz.
What are the motor cable length limits?
The maximum motor cable length is 50 m (164.04 ft) for shielded cable or 100 m (328.08 ft) for unshielded cable.
What is the mechanical variant and protection rating?
The frame size is FSE, and the degree of protection is IP20 / UL open type.
Is the configuration supplied with a control unit and BOP?
It is without a control unit and BOP. For a quotation, send the required quantity, destination, requested date, and project list context.