Key Features
- Rated input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz; rated current is 2.30 A for LO and 1.90 A for HO.
- Overload ratings: Rated output power is 0.55 kW for LO and 0.37 kW for HO. LO provides 150% for 3 s, 110% for 57 s and 100% for 240 s; HO provides 200% for 3 s, 150% for 57 s and 100% for 240 s.
- Control and output: Output frequency is 0 … 240 Hz for vector control and 0 … 550 Hz for V/f control. Supported control includes V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control.
- I/O and communication: The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact output, 1 transistor output, 1 differential analog/digital input, 1 non-isolated analog output and PROFIBUS DP.
- Connections and cable limits: Plug-in screw terminals are provided on the line side, motor end and DC link. The maximum shielded motor cable length is 50 m; the DC link line length, max., is 15 m.
- Protection and mounting data: Protection is IP20 / UL open type. Frame size is FSAA, with width 73 mm (2.87 in) and depth 155 mm (6.10 in).
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Input voltage | 380 … 480 V +10 % -20 % |
| Input frequency | 47 … 63 Hz |
| Rated output power (LO) | 0.55 kW | 0.75 hp |
| Rated output power (HO) | 0.37 kW | 0.50 hp |
| Output frequency for vector control | 0 … 240 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Communication | PROFIBUS DP |
| I/O | 6 digital inputs, 1 fail-safe digital input, 1 relay changeover contact output, 1 transistor output, 1 differential analog/digital input, 1 non-isolated analog output |
| Protection | IP20 / UL open type |
Frequently Asked Questions
What is the exact product and lifecycle status?
The product is Siemens 6SL3210-1KE11-8AP2, and its lifecycle is Active Product.
What are the LO and HO output ratings?
LO is 0.55 kW | 0.75 hp, and HO is 0.37 kW | 0.50 hp. The overload durations and percentages differ by rating.
Which control methods and communication interface are supported?
It supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control. Communication is PROFIBUS DP.
What I/O is included?
It has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact output, 1 transistor output, 1 differential analog/digital input and 1 non-isolated analog output.
What quantity and destination should be included in a quotation request?