Key Features
- Rated power and overload: Rated power is 1.10 kW | 1.50 hp for low overload and 0.75 kW | 1.00 hp for high overload. Low overload supports 150% for 3s, 110% for 57s and 100% for 240s; high overload supports 200% for 3s, 150% for 57s and 100% for 240s.
- Supply and output: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, rated voltage 400V IEC | 480V NEC, with maximum output current of 4.40 A.
- Control techniques: The converter supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control.
- I/O interface: The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 digital output as relay changeover contact, 1 digital output as transistor, 1 differential analog / digital input and 1 non-isolated analog output.
- Communication and safety: Fieldbus: PROFIBUS DP. Safe Torque Off is integrated.
- Connections and protection: Line-side and motor-end connections use plug-in screw terminals. Protection: IP20 / UL open type; frame size: FSAA.
Technical Summary
| Product lifecycle | Active Product |
|---|---|
| Rated power (LO) | 1.10 kW | 1.50 hp |
| Rated power (HO) | 0.75 kW | 1.00 hp |
| Input voltage | 380 … 480 V +10 % -20 % |
| Line frequency | 47 … 63 Hz |
| Communication | PROFIBUS DP |
| I/O interface | 6DI, 2DO, 1AI, 1AO, 1Mot_t |
| Protection | IP20 / UL open type |
Frequently Asked Questions
What are the rated power options for Siemens 6SL3210-1KE13-2AP2?
Rated power is 1.10 kW | 1.50 hp for low overload and 0.75 kW | 1.00 hp for high overload.
Which control and feedback interfaces does this converter have?
It has 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog / digital input and 1 non-isolated analog output. PROFIBUS DP is the fieldbus, and Safe Torque Off is integrated.
What connectors and motor cable limit are specified?
Line-side and motor-end connections use plug-in screw terminals. Maximum motor cable length is 50 m (164.04 ft) for shielded cable.
What protection and mechanical variant does it use?
Protection is IP20 / UL open type, with frame size FSAA, width 73 mm (2.87 in) and depth 155 mm (6.10 in).
What information should I include for a quotation?
Please provide the required quantity and destination, together with any requested date or project list context.