Overview
Key Features
- Rated power and overload: Rated power: 18.50 kW | 25.00 hp (LO) and 15.00 kW | 20.00 hp (HO). Low overload: 150% for 3s, 110% for 57s, 100% for 240s; high overload: 200% for 3s, 150% for 57s, 100% for 240s.
- Supply and frequency: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output: 3 AC, rated voltage 400V IEC | 480V NEC.
- Control and communication: Supports V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law and sensorless vector control. Communication: PROFIBUS DP.
- I/O interface: Standard digital inputs: 6; fail-safe digital inputs: 1; digital outputs: 1 as relay changeover contact and 1 as transistor; analog/digital inputs: 1 differential input; analog outputs: 1 non-isolated output. Safe Torque Off is integrated.
- Connections and cable limits: Line-side and motor-end connections use plug-in screw terminals. Maximum motor cable length: 50 m (164.04 ft) shielded; DC link line length, max.: 15 m (49.21 ft).
- Mechanical configuration and protection: Frame size: FSC. Dimensions: 140 mm (5.51 in) width and 203 mm (7.99 in) depth. Degree of protection: IP20 / UL open type; cooling uses an integrated fan.
Technical Summary
| Product type | SINAMICS G120C compact converter |
|---|---|
| Input supply | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated power (LO) | 18.50 kW | 25.00 hp |
| Rated power (HO) | 15.00 kW | 20.00 hp |
| Rated current (LO) | 37.00 A output |
| Rated current (HO) | 31.00 A output |
| Max. output current | 62.00 A |
| Communication | PROFIBUS DP |
| I/O interface | 6DI, 2DO, 1AI, 1AO, 1 fail-safe digital input |
| Protection | IP20 / UL open type |
| Frame size | FSC |
Frequently Asked Questions
What is the rated power of Siemens 6SL3210-1KE23-8AP1?
Rated power is 18.50 kW | 25.00 hp under low overload (LO) and 15.00 kW | 20.00 hp under high overload (HO).
Which communication and I/O interfaces does this SINAMICS G120C have?
It has PROFIBUS DP, 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 analog/digital differential input and 1 non-isolated analog output.
What are the connection and motor cable specifications?
Line-side and motor-end connections use plug-in screw terminals. Maximum shielded motor cable length is 50 m (164.04 ft); the DC link line length, max., is 15 m (49.21 ft).
What protection and mechanical configuration does it have?
It has IP20 / UL open type protection and FSC frame size. Dimensions are 140 mm (5.51 in) wide and 203 mm (7.99 in) deep.
How can I request a quotation for this exact model?
Send the required quantity, destination and requested date for a model-specific quotation.