  • Rated current and power: Rated operational current: 38 A at 40 °C. Standard circuit power: 18.5 kW at 400 V and 22 kW at 500 V, both at 40 °C.
  • Operating voltage and frequency: Operating voltage at standard circuit: 400 … 600 V, with -15 % relative negative tolerance and 10 % relative positive tolerance. Rated operating frequency: 50 … 60 Hz.
  • Control supply: Control supply voltage: 110 … 230 V AC at 50 Hz or 60 Hz, and 110 … 230 V DC. Control supply voltage type: AC/DC.
  • Protection and functions: Has an integrated bypass contact system, thyristors, intrinsic device protection, motor overload protection, external reset and adjustable current limitation. Evaluation of thermistor motor protection, inside-delta circuit and motor brake output are not included.
  • Installation and connections: S0 device with screw and snap-on mounting, 45 mm width, 125 mm height and 155 mm depth. Main, auxiliary and control circuits use screw-type terminals; the front has IP20 protection according to IEC 60529.

Technical Summary

Product designation Soft starter
Rated operational current 38 A at 40 °C
Standard circuit power 18.5 kW at 400 V; 22 kW at 500 V, both at 40 °C
Operating voltage 400 … 600 V at standard circuit
Operating frequency 50 … 60 Hz
Control supply 110 … 230 V AC/DC
Device size S0
Mounting Screw and snap-on mounting
Connections Screw-type terminals
Front protection IP20 according to IEC 60529
Operating ambient temperature -25 … +60 °C

Frequently Asked Questions

What is the rated current of Siemens 3RW4028-1BB15?

The rated operational current is 38 A at 40 °C, 34 A at 50 °C and 31 A at 60 °C.

What supply voltage does this soft starter use?

The operating voltage at standard circuit is 400 … 600 V. The control supply is 110 … 230 V AC at 50 Hz or 60 Hz, or 110 … 230 V DC.

How is the 3RW4028-1BB15 mounted and connected?

It uses screw and snap-on mounting. The main, auxiliary and control circuits use screw-type terminals.

Which protection functions are included?

It has intrinsic device protection, motor overload protection, external reset and adjustable current limitation. It does not include evaluation of thermistor motor protection.

What details should I provide for a quotation?

Provide the required quantity, destination and requested date so the exact Siemens model can be reviewed for quotation.

Quote checklist

Quote requirements

Add the details below to help us check availability and prepare a quote for this model.

  • Model or MLFB
  • Quantity and destination
  • Required condition
  • Nameplate or product photo (optional)

Product inquiry

Request a Quote